※2-3 Bulb Mode Set
1. Press or key to select "ON" or "OFF" and press key to determine.
ON : Bulb mode operation is conducted. (For unit equipped with humidity sensor)
OFF : Bulb mode operation is not conducted.
2. After selecting "ON", press
or key to select "L", "H-L", or "H" for the EFM speed and press
key to determine.
3. Press or key to select the defrost completion temperature in the range of 4.0℃ to 18.0℃ and
press
key to determine.
※ If it is necessary to set the humidity, do so according to the procedure in 2-2 Dehumidification Set.
※2-4 USDA Set
1. Press key to select number of sensors and press key to determine.
4 sensors :4 USDA sensors connected
3 sensors :3 USDA sensors connected
AUTO :
Automatically recognize the number
of USDA sensors connected (Note 1)
OFF :No USDA sensor connected
Note 1: To measure the temperature inside or cargo
temperature for the purposes other than cold
treatment transport, USDA sensor can record the
temperature ranging from –30.0 ℃ to +40 ℃ .
Do not use it for cold transport treatment
because it does not meet the USDA standards.
USDA
▲▼ : Change
ENTER : Confirm
OFF
▲▼ : Change
ENTER : Confirm
4 sensors
USDA
Dehumidification Set
▲▼:Change
ENTER:Confirm
▲▼:Change
ENTER:Confirm
ON
Dehumidification Set
▲▼:Change
ENTER:Confirm
95 % RH
Humidity Setpoint
▲▼:Change
ENTER:Confirm
75 % RH
Humidity Setpoint
OFF
1. Dehumidification set
2. Humidity setpoint selection
Mode Set screen
Bulb mode
▲▼:Change
ENTER:Confirm
▲▼:Change
ENTER:Confirm
ON
Bulb mode
OFF
1. Bulb mode selection 2. EFM speed setting
3. Defrost completion temperature
Mode Set screen
Evap Fan Speed
Def
End
Temp
Bulb mode
18.0℃
▲▼:Change
ENTER:
Confirm
L
Evap Fan Speed
Def
End
Temp
Bulb mode
15.0℃
▲▼:Change
ENTER:
Confirm
L