Si30-408 Control of Indoor Unit
Basic Information 33
4.5 Thermostat Control in Cooling / Heating Automatic
Operation
In cooling / heating automatic operation, the unit is controlled as shown below based on set
"differential value". Factory setting of differential valve is 5°C. As to charging method of setting
value, refer to page 43 and page 44.
Cooling/Heating
Differential: at
5°C
Automatic heating
22˚C
Automatic cooling
27˚C
Display selection
CoolingHeating
Display selection
HeatingCooling
Cooling thermostat ON
Cooling thermostat OFF
3˚C
Heating thermostat OFF
Heating thermostat ON
T=5˚C
T/2+2˚C(4.5˚C)
Cooling / heating differential : at 3˚C
Automatic heating
22˚C
Automatic cooling
25˚C
T=3˚C

Table of Contents

Other manuals for Daikin VRV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV and is the answer not in the manual?

Daikin VRV Specifications

General IconGeneral
BrandDaikin
Energy EfficiencyHigh
ControlCentralized and individual zone control
Inverter TechnologyYes
TypeVariable Refrigerant Volume (VRV)
Cooling CapacityVaries by model
Heating CapacityVaries by model
RefrigerantR-32 or R-410A
ApplicationCommercial buildings, large residential spaces
SEERVaries by model
HSPFVaries by model
EERVaries by model
COPVaries by model
Sound LevelVaries by model
Indoor Unit Optionswall-mounted, ducted

Related product manuals