Parameter Meaning
SENSOR CALIBRATION OUTD
SYSTEM SUPPLY
SUPPLY LINE
RETURN LINE
HOT WATER
HOT WATER TOP
REFR 1
REFR 2
DISCH. PIPE
DEFR SENSOR
BUFFER TANK
DISTRIBUTION CIRCUIT 1
DISTRIBUTION CIRCUIT 2
POOL
SUCTION GAS
Factory setting: 0, range: -5°C – 5°C
EXTERNAL FACTOR: Affects sensors that are installed inside the heat pump.
Factory setting: 0, range: 0°C – 20°C
VERSION Indicates the version number of the software in the control.
DISPLAY
HUB
HP (heat pump card)
EXP (expansion card)
EXV (expansion valve card)
LOG TIME Time interval between collection points of temperature history in minutes. The history graphs
always show the 60 last collection points, which means that the graphs can display history
from 1 hour up to 60 hours ago.
(The function is not active if there is an active alarm).
Factory setting: 1M, range: 1M – 60M
10.8 DEFROST
Parameter Meaning
DEFR OFFSET Adjusting the defrost curve. Negative value moves the defrost curve down which means
that it takes a longer time before defrosting starts. Positive value moves the defrost curve
up which means that it takes a shorter time before defrosting starts.
Factory setting: 0°C, range: -20°C – 20°C
STOP DEFR The temperature that refrigerant sensor 2 must reach to complete a defrost.
Factory setting: 38°C, range: 7°C – 60°C
60 – Installation instructions VMGFD102

Table of Contents

Other manuals for Danfoss DHP-AQ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss DHP-AQ and is the answer not in the manual?

Danfoss DHP-AQ Specifications

General IconGeneral
BrandDanfoss
ModelDHP-AQ
CategoryHeat Pump
LanguageEnglish

Related product manuals