EasyManuals Logo
Home>Danfoss>Controller>EKE 347

Danfoss EKE 347 User Manual

Danfoss EKE 347
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
User Guide | Liquid level controller, EKE 347
© Danfoss | DCS (ADAP-KOOL®) | 2016-04
DKRCI.PD.RP0.A4.02 | 6
Setup & service menu - COMMISSIONING
Parameter Options
Default
values
Reference Main switch On, O O
Liquid level setpoint 0 - 100% 50.0%
Operation mode Master, IO, Slave Master
Alarm setup Lower level limit 0 - 100% 15%
Upper level limit 0 - 100% 85%
Level alarm mode Time, Hysteresis Time
Lower delay 0 - 999 sec 10 sec
Upper delay 0 - 999 sec 50 sec
Lower level hysteresis 0-20 % 3%
Upper level hysteresis 0-20 % 5%
Function common alarm Not follow; Follow up; Follow low; Follow all Not follow
Oscillation detect band 0 - 100% 100%
Oscillation detect timeout 2 - 30 min 20 min
Force pump OFF in stop mode Yes / No No
IO Lower level limit 0 - 100% 5%
IO Upper level limit 0 - 100% 95%
IO Lower level hysteresis 0-20 % 3%
IO Upper level hysteresis 0-20 % 3%
IO Lower delay 0 - 999 sec 10 sec
IO Upper delay 0 - 999 sec 50 sec
IO Level limit 0 - 100% 50%
IO Level delay 0 - 999 sec 10 sec
IO Level hysteresis 0-20 % 3%
IO Level action Falling,Rising Falling
Control Control Method On/O ,P, PI PI
Regulating principle Low, High Low
P-band 5 - 200% 30.0%
Integration time Tn 60 - 600 sec 400 sec
Neutral zone 0 - 25% 2.0%
Dierence 0,5-25% 2%
Period time for AKV/AKVA 3-15 sec 6 sec
Minimum OD 0 - 99% 0%
Maximum OD 1 - 100% 100%
Display Language EN,CN,PT,RU,SP,FR,IT, GER, ARAB EN
Output indication level, OD Level
Login timeout 1 - 120 min 10 min
Backlight timeout 0 - 120 min 2 min
Password daily 3 -digit, 0 - 999 100
Password service 3 -digit, 0 - 999 200
Password commission 3 -digit, 0 - 999 300
IO cong System conguration ICAD+NC, ICAD, AKV/A+NC, AKV/A, NC only ICAD + NC
Level signal setup AKS 4100, AKS 41, Current, Voltage AKS4100
Voltage at low liquid level 0-10V 0 V
Voltage at high liquid level 0 -10V 10 V
Current at low liquid level 0-20 mA 4 mA
Current at high liquid level 0-20 mA 20 mA
Valve position setup Not used, Current, Voltage Not used
Voltage at closed valve position 0-10V 0 V
Voltage at open valve position 0-10V 10 V
Current at closed valve position 0-20 mA 4 mA
Current at open valve position 0-20 mA 20 mA
Common alarm setup D04, High alarm, D03, Disp only High alarm
Multiple valve setup Not used, 2 same cap, 2 dif cap, 3 same cap, 3 dif cap Not used
Multiple valve pattern Parallel,Sequence Parallel
Valve A capacity 0-100 % 50%
Valve B capacity 0-100 % 50%
Valve C capacity 0-100 % 30%
ICAD takeover OD 0-100% 80%
IO module setup Used, Not used Not used
Communication CAN ID 1 - 127 1
CAN baudrate 20k, 50k, 125k, 250k, 500k, 1M 500k
Modbus ID 0 - 120 1
Modbus baudrate 0, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400 19200
Modbus mode 8N1, 8E1, 8N2 8E1
Modbus mapping Operation, Setup Operation
Valve B CAN ID 1 - 127 2
Valve C CAN ID 1 - 127 3
IO Mod. CAN ID 1 - 127 4
To be continued......

Other manuals for Danfoss EKE 347

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKE 347 and is the answer not in the manual?

Danfoss EKE 347 Specifications

General IconGeneral
BrandDanfoss
ModelEKE 347
CategoryController
LanguageEnglish

Related product manuals