-30 °C…60 °C (-22 °F…140 °F)
7.4.1 I/O Specifications
Control inputs and outputs are PELV galvanically isolated from supply voltage and other high voltage terminals, unless otherwise
specified.
Analog Input
Table 30: Analog Input
Voltage range: -10 V to 10 V (scalable)
Input impedance: 10 kΩ
Maximum voltage: +12 V/-12 V
Current range: 0/4-20 mA (scalable)
Input impedance: 200 Ω
Maximum current: 24 mA
Temperature sensor support
(2)
1xPt100, 2x Pt100, 3xPt100, Pt1000, Ni1000 (A/B), KTY81, KTY82, KTY84
1
The selection is made in the software. For more information, refer to the application guide.
2
External insulation of the sensor is required to comply with PELV.
Analog Output
Table 31: Analog Output
Minimum load resistor to GND
AQ390830267692en-000601 / 136R027350 | Danfoss A/S © 2023.06
General Purpose I/O Installation
and Configuration
Functional Extension Options
Operating Guide