Label ID
Parameter
name
Description and selection
options
Min.
Max.
Factory set‐
ting
Modbus
address
Alterna‐
tive
Modbus
address
Size in
bytes
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Persis‐
tent
Yes/No
Modbus
func‐
tion
ID4
Requested
Opening
Degree (set-
point)
Set the desired opening
degree Only when main
switch is set to manual
(ID1=1) 0…100% (min step
– 1%)
1
100
0
3003
3303
1
1 - 1
RW
No
3 & 6, 16
ID203
Requested
Opening
Degree (set-
point)
The opening degree re‐
quested through Modbus
Only active when Main
switch is set to auto (ID1=0)
and input signal is set to
Modbus (ID3=4). 0…10000
points, where 100 = 1%
(i.e. 5021 = 50.21%; 10000 =
100.00%)
0
10000
0
3004
3304
2
1 - 1
RW
No
3 & 6, 16
ID24
Service
passcode
(Level 2)
Change password for level
2 acess.
Level 2 will give acess to
read/write parameters of
level 2. See Column "Pass-
word level to Read - Write"
and "Read only / Read Write"
0
99999999
12131400
3005 …
3006
4
2
W
Yes
16
Service/Advanced Control Parameters
Label ID
Parameter
name
Description and selection
options
Min.
Max.
Factory set‐
ting
Modbus
address
Alterna‐
tive
Modbus
address
Size in
bytes
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Persis‐
tent
Yes/No
Modbus
func‐
tion
ID5
Speed
positive, 3-
point
Opening speed Only active
when Operation mode (ID2)
is set to 3-point.
Percentage of full
speed.1...100% (min step –
1%)
1
100
10
3011
1
2 - 2
RW
Yes
3 & 6, 16
ID75
Speed
negative, 3-
point
Closing speed Only active
when Operation mode (ID2)
is set to 3-point.
Percentage of full
speed.1...100% (min step –
1%)
1
100
10
3012
1
2 - 2
RW
Yes
3 & 6, 16
ID6
Speed
positive,
on/o
Opening speed Only active
when Operation mode (ID2)
is set to ON/OFF.
Percentage of full speed
1...100% (min step – 1%)
1
100
100 - ICAD
600; 50 -
ICAD 1200
3013
1
2 - 2
RW
Yes
3 & 6, 16
ID76
Speed
negative,
on/o
Closing speed Only active
when Operation mode (ID2)
is set to ON/OFF.
Percentage of full speed
1...100% (min step – 1%)
1
100
100 - ICAD
600; 50 -
ICAD 1200
3014
1
2 - 2
RW
Yes
3 & 6, 16
ID7
Speed,
modulating
Speed while modulating
Only active when Operation
mode (ID2) is set to Modu-
lating.
Percentage of full speed
1...100% (min step – 1%)
For CVE valve max value =
50%
1
100
100 - ICAD
600; 50 -
ICAD 1200
3015
1
2 - 2
RW
Yes
3 & 6, 16
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 19
ICM and ICMTS Motorized Valves with ICAD Actuators

Table of Contents

Other manuals for Danfoss ICAD 1200B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ICAD 1200B and is the answer not in the manual?

Danfoss ICAD 1200B Specifications

General IconGeneral
BrandDanfoss
ModelICAD 1200B
CategoryControl Unit
LanguageEnglish

Related product manuals