Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Requested
Opening
Degree (set-
point)
Set the desired opening
degree Only when main
switch is set to manual
(ID1=1) 0…100% (min step
– 1%)
Requested
Opening
Degree (set-
point)
The opening degree re‐
quested through Modbus
Only active when Main
switch is set to auto (ID1=0)
and input signal is set to
Modbus (ID3=4). 0…10000
points, where 100 = 1%
(i.e. 5021 = 50.21%; 10000 =
100.00%)
Change password for level
2 acess.
Level 2 will give acess to
read/write parameters of
level 2. See Column "Pass-
word level to Read - Write"
and "Read only / Read Write"
Service/Advanced Control Parameters
Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Opening speed Only active
when Operation mode (ID2)
is set to 3-point.
Percentage of full
speed.1...100% (min step –
1%)
Closing speed Only active
when Operation mode (ID2)
is set to 3-point.
Percentage of full
speed.1...100% (min step –
1%)
Opening speed Only active
when Operation mode (ID2)
is set to ON/OFF.
Percentage of full speed
1...100% (min step – 1%)
100 - ICAD
600; 50 -
ICAD 1200
Closing speed Only active
when Operation mode (ID2)
is set to ON/OFF.
Percentage of full speed
1...100% (min step – 1%)
100 - ICAD
600; 50 -
ICAD 1200
Speed while modulating
Only active when Operation
mode (ID2) is set to Modu-
lating.
Percentage of full speed
1...100% (min step – 1%)
For CVE valve max value =
50%
100 - ICAD
600; 50 -
ICAD 1200
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 19
ICM and ICMTS Motorized Valves with ICAD Actuators