MCD 200 Design Guide
MG.17.C3.02 – VLT is a registered Danfoss trademark 13
MCD 201
■ Control Circuits
2 Wire Control
A3
A1
A2
N1
N2
START/
STOP
*
380-440 VAC (CV3)
110-240 VAC (CV3)
OR
24 VAC/VDC (CV1)
A3
A1
A2
N1
N2
START/
STOP
*
(+)
(-)
177HA209.12
* Also resets the MCD 201
3 Wire Control
380-440 VAC (CV3)
A3
A1
A2
N1
N2
START
STOP
*
A3
A1
A2
N1
N2
START
STOP
*
(+)
(-)
110-240 VAC (CV3)
OR
24 VAC/VDC (CV1)
177HA210.11
* Also resets the MCD 201
■
Functionality
User Adjustments
177HA248.11
70%
60%
50%
40%
30%
10s
Full
Voltage Start
(seconds)
2s
4s
6s
8s 12s
14s
16s
20s
10s
No
Soft Stop
(seconds)
2s
4s
6s
8s 12s
14s
16s
20s
Ramp Down
U
Initial Torque
U
Ramp Up
U
(% U)
1 Initial Torque
Value:
30% - 75% Initial Torque
✭ 75%
Function:
Determines the start torque generated by the motor
when the start command is first applied.
Description of choice:
Set so that the motor begins to rotate as soon as the
start command is given.
2Ramp Up
Value:
2 - 20 seconds, Full Voltage
✭ 10 seconds
Function:
Determines the time taken for voltage to be ramped up
to line voltage.
Description of choice:
Set to optimise motor acceleration and/or start
current. Short ramp times result in quicker acceleration
and higher start currents. Long ramp times result in
slower acceleration and lower start current.
3Ramp Down
Value:
2 - 20 seconds, No Soft Stop
✭ No Soft Stop
Function:
Sets the time of the soft stop voltage ramp. The soft
stop function extends motor deceleration time by
ramping down voltage supplied to the motor when a
stop is initiated.