EasyManuals Logo
Home>Danfoss>Controller>MCD 201

Danfoss MCD 201 User Manual

Danfoss MCD 201
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
MCD 200 Design Guide
MG.17.C3.02 – VLT is a registered Danfoss trademark 9
MCD 200 Series Overview
Cable Size
mm
2
(AWG)
0.14 - 1.5
(26 - 16)
0.14 - 1.5
(26 - 16)
N.A.
3.5 mm
0.5 Nm max
4.4 lb-in max
mm
2
(AWG)
N.A.
N.A.
MCD 200-075 ~
MCD 200-110
10 - 35
(8 - 2)
10 - 35
(8 - 2)
Torx (T20)
3 Nm
2.2 ft-lb
7 mm
3 Nm
2.2 ft-lb
MCD 200-007 ~
MCD 200-030
25 - 50
(4 - 1/0)
25 - 50
(4 - 1/0)
Torx (T20)
4 Nm
2.9 ft-lb
7 mm
4 Nm
2.9 ft-lb
MCD 200-037 ~
MCD 200-055
MCD 200-007 ~
MCD 200-110
N.A.
N.A.
26
(1.02)
11
(0.43)
8.5
(0.33)
14
(0.55)
mm (inch) mm (inch)
14
(0.55)
mm (inch) mm (inch)
6
(0.24)
177HA245.12
75ºC Wire. Use copper conductors only.
Semiconductor Fuses
Semiconductor fuses may be used with the MCD
200 soft starters. Use of semiconductor fuses will
provide Type 2 coordination and reduce the potential
of SCR damage due to transient overload currents
and short circuits. MCD 200 soft starters have been
tested to achieve Type 2 coordination with
semiconductor fuses. The following table provides a
list of suitable Ferraz and Bussman fuses. If selecting
alternate brands ensure the selected fuse has a
lower total clearing I
2
t rating than the SCR, and can
carry start current for the full starting duration.
MCD 200 SCR I
2
t
(A
2
s)
Ferraz Fuse
European/IEC Style
(North American Style)
Bussman Fuse
Square Body
(170M)
Bussman Fuse
British Style
(BS88)
MCD 200-007 1150
6.6URD30xxxA0063
(A070URD30xxx0063)
170M-1314
63 FE
MCD 200-015 8000
6.6URD30xxxA0125
(A070URD30xxx0125)
170M-1317
160 FEE
MCD 200-018 10500
6.6URD30xxxA0160
(A070URD30xxx0160)
170M-1318
160 FEE
MCD 200-022 15000
6.6URD30xxxA0160
(A070URD30xxx0160)
170M-1318
180 FM
MCD 200-030 18000
6.6URD30xxxA0160
(A070URD30xxx0160)
170M-1319
180 FM
MCD 200-037 51200
6.6URD30xxxA0250
(A070URD30xxx0250)
170M-1321
250 FM
MCD 200-045 80000
6.6URD30xxxA0315
(A070URD30xxx0315)
170M-1321
250 FM
MCD 200-055 97000
6.6URD30xxxA0315
(A070URD30xxx0315)
170M-1321
250 FM
MCD 200-075 168000
6.6URD31xxxA0450
(A070URD31xxx0450)
170M-1322
500 FMM
MCD 200-090 245000
6.6URD31xxxA0450
(A070URD31xxx0450)
170M-3022
500 FMM
MCD 200-110 320000
6.6URD31xxxA0450
(A070URD31xxx0450)
170M-3022
500 FMM
xxx = Blade Type.
Refer Ferraz for options.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss MCD 201 and is the answer not in the manual?

Danfoss MCD 201 Specifications

General IconGeneral
BrandDanfoss
ModelMCD 201
CategoryController
LanguageEnglish

Related product manuals