MCD 200 Design Guide
4 MG.17.C3.02 – VLT is a registered Danfoss trademark
MCD 200 Series Overview
■ Ratings
Continuous Ratings (Internally bypassed) @ 40
o
C Ambient Temperature,
<1000 metres ✮
MCD 200
Model
Normal Heavy
007 18 A: AC53b 4-6:354 17 A: AC53b 4-20:340
015 34 A: AC53b 4-6:354 30 A: AC53b 4-20:340
018 42 A: AC53b 4-6:354 36 A: AC53b 4-20:340
022 48 A: AC53b 4-6:354 40 A: AC53b 4-20:340
030 60 A: AC53b 4-6:354 49 A: AC53b 4-20:340
037 75 A: AC53b 4-6:594 65 A: AC53b 4-20:580
045 85 A: AC53b 4-6:594 73 A: AC53b 4-20:580
055 100 A: AC53b 4-6:594 96 A: AC53b 4-20:580
075 140 A: AC53b 4-6:594 120 A: AC53b 4-20:580
090 170 A: AC53b 4-6:594 142 A: AC53b 4-20:580
110 200 A: AC53b 4-6:594 165 A: AC53b 4-20:580
Continuous Ratings (Internally bypassed) @ 50
o
C Ambient Temperature,
<1000 metres ✮
MCD 200
Model
Normal Heavy
007 17 A: AC53b 4-6:354 15 A: AC53b 4-20:340
015 32 A: AC53b 4-6:354 28 A: AC53b 4-20:340
018 40 A: AC53b 4-6:354 33 A: AC53b 4-20:340
022 44 A: AC53b 4-6:354 36 A: AC53b 4-20:340
030 55 A: AC53b 4-6:354 45 A: AC53b 4-20:340
037 68 A: AC53b 4-6:594 59 A: AC53b 4-20:580
045 78 A: AC53b 4-6:594 67 A: AC53b 4-20:580
055 100 A: AC53b 4-6:594 87 A: AC53b 4-20:580
075 133 A: AC53b 4-6:594 110 A: AC53b 4-20:580
090 157 A: AC53b 4-6:594 130 A: AC53b 4-20:580
110 186 A: AC53b 4-6:594 152 A: AC53b 4-20:580
✮ Contact Danfoss for other ratings.
Example
For 22 kW model 48 A: AC53b: 4-6:354
48 A: Starter current rating.
AC53b: Load category for soft starters with SCRs bypassed during run.
4-6: 400% start current for 6 seconds.
354: 354 seconds between the end of one start to the beginning of the next start (i.e. 10 starts per
hour).