Parameter Condition for value change
P3292-P3300 Leave at default value unless source addresses conflict with other nodes on the CAN bus or another addressing scheme is
desired
P3301 Data is sent at the rate of "value" x 10ms
P3308-P3309 Set to 0 if not using messages, otherwise data is sent at the rate of "value" x 10ms
P3302-P3307 Set to over 0 if using messages to send data at the rate of "value" x 10ms, otherwise messages are disabled
P3327 Set to over 0 if using messages to send data at the rate of "value" x 10ms, otherwise messages are disabled
P3331 Set to over 0 if using messages to send data at the rate of "value" x 10ms, otherwise messages are disabled
Application Guide
PVED-CLS startup guide
Parameter setting