230 Frequency bypass 1 (FREQ. BYPASS 1)
231 Frequency bypass 2 (FREQ. BYPASS 2)
232 Frequency bypass 3 (FREQ. BYPASS 3)
233 Frequency bypass 4 (FREQ. BYPASS 4)
Value:
0.0 - parameter 200
0.0 Hz
Function:
Some systems call for some output frequencies to be
avoided because of resonance problems in the sys-
tem.
Description of choice:
Enter the frequencies to be avoided.
See also parameter 229.
234 Motor phase monitor
(MOTOR PHASE MON)
Value:
Enable (ENABLE) [0]
Disable (DISABLE) [1]
Function:
In this parameter it is possible to select monitoring of
the motor phases.
Description of choice:
If Enable is selected, the adjustable frequency drive will
react on a missing motor phase which will result in
alarm 30, 31 or 32.
If Disable is selected, no alarm is given if a motor phase
is missing. The motor can be damaged/overheated if
it runs on only two phases. It is therefore recommen-
ded to keep the missing motor phase function ENA-
BLED.
VLT
®
5000 Series
108 MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.

Table of Contents

Other manuals for Danfoss VLT 5003

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5003 and is the answer not in the manual?

Danfoss VLT 5003 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5003
CategoryDC Drives
LanguageEnglish

Related product manuals