Operation & Display
001 Language
(LANGUAGE)
Value:
English (ENGLISH) [0]
German (DEUTSCH) [1]
French (FRANCAIS) [2]
Danish (DANSK) [3]
Spanish (ESPAÑOL) [4]
Italian (ITALIANO) [5]
Function:
The choice in this parameter defines the language to
be used on the display.
Description of choice:
There is a choice of English [0], German [1], French [2],
Danish [3], Spanish [4] and Italian [5].
002 Local/remote control
(OPERATION SITE)
Value:
Remote control (REMOTE) [0]
Local control (LOCAL) [1]
Function:
There is a choice of two methods of controlling the ad-
justable frequency drive.
Description of choice:
If Remote control [0] is selected, the adjustable fre-
quency drive can be controlled via:
1. The control terminals or the serial communi-
cation port.
2. The [START] key. However, this cannot over-
rule Stop commands (also start-disable) en-
tered via the digital inputs or the serial
communication port.
3. The [STOP], [JOG] and [RESET] keys, pro-
vided that these are active (see parameter
014, 015 and 017).
If Local control [1] is selected, the adjustable frequency
drive can be controlled via:
1. The [START] key. However, this cannot over-
ride Stop commands on the digital terminals
(if [2] or [4] has been selected in parameter
013).
2. The [STOP], [JOG] and [RESET] keys, pro-
vided that these are active (see parameter
014, 015 and 017).
3. The [FWD/REV] key, provided that this has
been activated in parameter 016 and that in
parameter 013 a choice of [1] or [3] has been
made.
4. Via P003 the local reference can be control-
led by means of the "Arrow up" and "Arrow
down" keys.
5. An external control command that can be
connected to terminal 16, 17, 19, 27, 29, 32
or 33. However, [2] or [4] must be selected in
parameter 013.
See also section Shift between local and remote con-
trol.
003 Local reference
(LOCAL REFERENCE)
Value:
Par. 013 set for [1] or [2]:
0 - f
MAX
50 Hz
Par. 013 set for [3] or [4] and par. 203 = [0]
set for:
Ref
MIN
- Ref
MAX
0.0
Function:
This parameter allows manual setting of the desired
reference value (speed or reference for the selected
configuration, depending on the choice made in pa-
rameter 013).
The unit follows the configuration selected in parame-
ter 100, provided Process control, closed-loop [3] or
Torque control, open-loop [4] has been selected.
Description of choice:
Local [1] must be selected in parameter 002 for this
parameter to be used.
The set value is saved in the case of a voltage drop-
out, see parameter 019.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 79
Programming

Table of Contents

Other manuals for Danfoss VLT 5003

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5003 and is the answer not in the manual?

Danfoss VLT 5003 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5003
CategoryDC Drives
LanguageEnglish

Related product manuals