Torque control, speed feedback
A winder winds material onto a roll or unwinds material
from a roll at a constant tension.
A device measures the radius of the roll and adjusts
the motor torque to ensure that the tension is constant.
The measuring device must have a non-linear output
signal.
The following must be programmed in order shown:
Function:
Parameter: Setting: Data value:
Configuration 100 Torque control, speed feedback[5]
Rotation, frequency/direction 200 Both directions, 0-132 Hz [1]
Reference/feedback range 203 -Max. - +Max. [1]
Minimum reference 204 Set to min. torque (Nm)
Maximum reference 205 Set to max. torque (Nm)
Reference function 214 Relative [1]
Terminal 32, encoder input A 306 Encoder feedback, input A [25]
Terminal 33, encoder input B 307 Encoder feedback, input B [24]
Encoder feedback, pulses/rev. 329 Set to encoder pulses per rev.
Terminal 53, analog input 308 Reference [1]
Terminal 54, analog input 311 Relative reference [4]
Speed PID lowpass filter 421 10 msec.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 171
Examples of use

Table of Contents

Other manuals for Danfoss VLT 5003

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5003 and is the answer not in the manual?

Danfoss VLT 5003 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5003
CategoryDC Drives
LanguageEnglish

Related product manuals