Conveyor belt
A conveyor belt is to be controlled using the digital in-
puts. Start the conveyor belt going to the right (clock-
wise) via switch 2 and to the left (anti-clockwise) via
switch 3. The reference will increase as long as switch
5 (speed up) is active and will be reduced when switch
6 (speed down) is active.
A stop via the ramp can be activated by means of con-
tact 1; quick-stop by means of switch 4.
1. Pulse stop (inverse)
2. Pulse start to the right
3. Pulse start to the left
4. Quick-stop
5. Speed up
6. Speed down
The following must be programmed in order shown:
Function:
Parameter: Setting: Data value:
Rotation, frequency/direction 200 Both directions, 0-132 Hz [1]
Minimum reference 204 3-10 (Hz)
Ramp-up time 1 207 10-20 sec.
Ramp-down time 1 208 10-20 sec.
Ramp-up time 2 209 10-20 sec.
Ramp-down time 2 210 10-20 sec.
Digital input, term. 16 300 Stop (inverse) [2]
Digital input, term. 17 301 Freeze reference [7]
Digital input, term. 18 302 Pulse start [2]
Digital input, term. 19 303 Start reversing [2]
Digital input, term. 27 304 Quick-stop (inverse) [2]
All other settings are based on factory settings. How-
ever, motor data (nameplate data) must always be
entered in parameters 102-106.