AC line supply 3 x 525-690 V
According to international requirements VLT type 5042 5052 5062 5072 5102
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (525-550 V)
56 76 90 113 137
I
VLT, MAX
(60 s) [A] (525-550
V)
62 84 99 124 151
I
VLT,N
[A] (551-690 V)
54 73 86 108 131
I
VLT, MAX
(60 s) [A] (551-690
V)
59 80 95 119 144
Output
S
VLT,N
[kVA] (550 V)
53 72 86 108 131
S
VLT,N
[kVA] (575 V)
54 73 86 108 130
S
VLT,N
[kVA] (690 V)
65 87 103 129 157
Typical shaft output
[kW] (550 V)
37 45 55 75 90
[HP] (575 V) 50 60 75 100 125
[kW] (690 V) 45 55 75 90 110
High overload torque (160 %):
Output current
I
VLT,N
[A] (525-550 V)
48 56 76 90 113
I
VLT, MAX
(60 s) [A] (525-550
V)
77 90 122 135 170
I
VLT,N
[A] (551-690 V)
46 54 73 86 108
I
VLT, MAX
(60 s) [A] (551-690
V)
74 86 117 129 162
Output
S
VLT,N
[kVA] (550 V)
46 53 72 86 108
S
VLT,N
[kVA] (575 V)
46 54 73 86 108
S
VLT,N
[kVA] (690 V)
55 65 87 103 129
Typical shaft output
[kW] (550 V)
30 37 45 55 75
[HP] (575 V) 40 50 60 75 100
[kW] (690 V) 37 45 55 75 90
Max. cable cross-section
to motor
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
Max. cable cross-section
to load sharing and brake
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (550 V)
60 77 89 110 130
I
L,N
[A] (575 V)
58 74 85 106 124
I
L,N
[A] (690 V)
58 77 87 109 128
High overload torque (160 %):
Rated input current
I
L,N
[A] (550 V)
53 60 77 89 110
I
L,N
[A] (575 V)
51 58 74 85 106
I
L,N
[A] (690 V)
50 58 77 87 109
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
Max. pre-fuses (line) [-]/UL
[A]
1
125 160 200 200 250
Efficiency
3
0.97 0.97 0.98 0.98 0.98
Power loss
Normal overload [W]
1458 1717 1913 2262 2662
High overload [W] 1355 1459 1721 1913 2264
Weight
IP 00 [kg]
82
Weight
IP 21/NEMA 1 [kg]
96
Weight
IP 54/NEMA 12 [kg] 96
Enclosure IP 00, IP 21/NEMA 1 and IP 54/NEMA 12
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with national and local
regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply and motor: M10; Brake and load sharing: M8
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 31
Technical data

Table of Contents

Other manuals for Danfoss VLT 5003

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5003 and is the answer not in the manual?

Danfoss VLT 5003 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5003
CategoryDC Drives
LanguageEnglish

Related product manuals