Two wire start/stop
-
Start/stop using terminal 18.
Parameter 302 = Start [1]
-
Quick-stop using terminal 27.
Parameter 304 = Coasting stop inverted [0]
Pulse start/stop
-
Stop inverted by means of terminal 16.
Parameter 300 = Stop inverted [2]
-
Pulse start using terminal 18.
Parameter 302 = Pulse start [2]
-
Jog by means of terminal 29.
Parameter 305 = Jog [5]
Setup change
-
Selection of setup using terminals 32 and 33.
Parameter 306 =Selection of setup, lsb [10]
Parameter 307 = Selection of setup, msb [10]
Parameter 004 = Multi-setup [5].
Digital speed up/down
-
Speed up and down using terminals 32 and
33.
Parameter 306 = Speed up [9]
Parameter 307 = Speed down [9]
Parameter 305 = Freeze reference [7].