Analog input 54 [V] (ANALOG INPUT 54 [V]) [18]
Analog input 60 [mA]
(ANALOG INPUT 60 [mA]) [19]
Pulse reference [Hz] (PULSE REF. [Hz]) [20]
External reference [%] (EXTERNAL REF
[%]) [21]
Status word [Hex] (STATUS WORD [HEX]) [22]
Brake effect/2 min. [KW]
(BRAKE ENERGY/2 min) [23]
Brake effect/sec. [kW] (BRAKE ENERGY/s) [24]
Heat sink temp. [°C] (HEATSINK TEMP [°C]) [25]
Alarm word [Hex] (ALARM WORD [HEX]) [26]
Control word [Hex]
(CONTROL WORD [HEX]) [27]
Warning word 1 [Hex]
(WARNING WORD 1 [HEX]) [28]
Warning word 2 [Hex]
(WARNING WORD 2 [HEX]) [29]
Communication option card warning
(Comm opt warn [hex]) [30]
RPM [min
-1
] (MOTOR RPM [RPM]) [31]
RPM x scaling [
-
] (MOTOR RPM x SCALE) [32]
LCP Display text (FREE PROG. ARRAY) [33]
Function:
This parameter allows a choice of the data value to be
displayed in line 2 of the display.
Parameters 010-012 enable the use of three additional
data values to be displayed in line 1.
Description of choice:
No readout switches of the readout.
Reference [%] corresponds to the total reference
(sum of digital/analog/preset/bus/freeze ref./catch-up
and slow-down).
Reference [unit] gives the status value of terminals
17/29/53/54/60 using the unit stated on the basis of
configuration in parameter 100 (Hz, Hz and rpm).
Feedback [unit] gives the status value of terminal
33/53/60 using the unit/scale selected in parameter
414, 415 and 416.
Frequency [Hz] gives the motor frequency, i.e. the
output frequency from the adjustable frequency drive.
Frequency x Scaling [-] corresponds to the present
motor frequency f
M
(without resonance dampening)
multiplied by a factor (scaling) set in parameter 008.
Motor current [A] states the phase current of the mo-
tor measured as effective value.
Torque [%] gives the current motor load in relation to
the rated motor torque.
Power [kW] states the actual power consumed by the
motor in kW.
Power [HP] states the actual power consumed by the
motor in HP.
Output energy [kWh] states the energy consumed by
the motor since the latest reset was made in parameter
618.
Motor voltage [V] states the voltage supplied to the
motor.
DC link voltage [V] states the intermediate circuit
voltage in the adjustable frequency drive.
Thermal load, motor [%] states the calculated/esti-
mated thermal load on the motor. 100% is the cut-out
limit.
Thermal load, VLT [%] states the calculated/estima-
ted thermal load on the adjustable frequency drive.
100% is the cut-out limit.
Hours run [Hours] states the number of hours that the
motor has run since the latest reset in parameter 619.
Digital input [Binary code] states the signal states
from the 8 digital terminals (16, 17, 18, 19, 27, 29, 32
and 33) Input 16 corresponds to the bit at the far left.
'0' = no signal, '1' = connected signal.
Analog input 53 [V] states the signal value on termi-
nal 53.
Analog input 54 [V] states the signal value on termi-
nal 54.
Analog input 60 [V] states the signal value on termi-
nal 60.
Pulse reference [Hz] states the possible frequency in
Hz connected to the terminals 17 or 29.
External reference [%] gives the sum of the external
reference as a percentage (the sum of analog/pulse/
bus).
Status word [Hex] gives the status word sent via the
serial communication port in Hex code from the ad-
justable frequency drive.
Brake power/2 min. [KW] states the brake power
transferred to an external brake resistor. The mean
power is calculated continuously for the latest 120 sec-
onds.
It is assumed that a resistor value has been entered in
parameter 401.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
82 MG.51.C5.22 - VLT