VLT
®
8000 AQUA
Programming
Analog/digital outputs
The two analog/digital outputs (terminals 42 and
45) can be programmed to show the present status
or a process value such as 0 - f
MAX
.
If the frequency converter is used as a digital output,
itgivesthepresentstatusbymeansof0or24VDC.
If the analog output is used for giving a process value,
there is a choice of three types of output signals:
0-20 mA, 4-20 mA or 0-32000 pulses
(depending on the value set in parameter 322 Terminal
45, output, pulse scaling. If the output is used as
a voltage output (0-10 V), a pull-down resistor of
470
(max. 500 ) should be fitted to terminal 39
(common for analog/digital outputs). If the output is
used as a current output, the resulting impedance of
the connected equipment should not exceed 500
.
Outputs terminal no. 42 45
parameter 319 321
Value:
No function (NO FUNCTION) [0] [0]
Drive ready (READY) [1] [1]
Standby (ENABLED & NO WARNING) [2] [2]
Running (RUNNING) [3] [3]
Running at ref. value (RUNNING AT REFERENCE) [4] [4]
Running, no warning (RUNNING NO WARNING) [5] [5]
Local reference active (DRIVE IN LOCAL REF.) [6] [6]
Remote references active (DRIVE IN REMOTE REF.) [7] [7]
Alarm (ALARM) [8] [8]
Alarm or warning (ALARM OR WARNING) [9] [9]
No alarm (NO ALARM) [10] [10]
Current limit (CURRENT LIMIT) [11] [11]
Safety interlock (SAFETY INTERLOCK) [12] [12]
Start command active (START SIGNAL APPLIED) [13] [13]
Reversing (REVERSE OPERATION) [14] [14]
Thermal warning (THERMAL WARNING) [15] [15]
Hand mode active (DRIVE IN HAND MODE) [16] [16]
Auto mode active (DRIVE IN AUTO MODE) [17] [17]
Sleep mode (SLEEP MODE) [18] [18]
Output frequency lower than f
LOW
parameter 223 (F OUT < F LOW) [19] [19]
Output frequency higher than f
HIGH
parameter 224 (F OUT > F HIGH) [20] [20]
Out of frequency range (FREQ. RANGE WARN.) [21] [21]
Output current lower than I
LOW
parameter 221 (I OUT < I LOW) [22] [22]
Output current higher than I
HIGH
parameter 222 (I OUT > I HIGH) [23] [23]
Out of current range (CURRENT RANGE WARN) [24] [24]
Out of feedback range (FEEDBACK RANGE WARN.) [25] [25]
Out of reference range (REFERENCE RANGE WARN) [26] [26]
Relay 123 (RELAY 123) [27] [27]
Mains imbalance (MAINS IMBALANCE) [28] [28]
Output frequency, 0 - f
MAX
0-20 mA (OUT. FREQ. 0-20 mA) [29] [29]
Output frequency, 0 - f
MAX
4-20 mA (OUT. FREQ. 4-20 mA) [30] [30]
Output frequency (pulse sequence), 0 - f
MAX
0-32000 p (OUT. FREQ. PULSE) [31] [31]
External reference, Ref
MIN
-Ref
MAX
0-20 mA (EXT. REF. 0-20 mA) [32] [32]
External reference, Ref
MIN
-Ref
MAX
4-20 mA (EXTERNAL REF. 4-20 mA) [33] [33]
External reference (pulse sequence), Ref
MIN
-Ref
MAX
0-32000 p (EXTERNAL REF. PULSE) [34] [34]
Feedback, FB
MIN
-FB
MAX
0-20 mA (FEEDBACK 0-20 mA) [35] [35]
Feedback, FB
MIN
-FB
MAX
4-20 mA (FEEDBACK 4-20 mA) [36] [36]
Feedback (pulse sequence), FB
MIN
-FB
MAX
0 - 32000 p (FEEDBACK PULSE) [37] [37]
Output current, 0 - I
MAX
0-20 mA (MOTOR CUR. 0- 20 mA) [38] [38]
Output current, 0 - I
MAX
4-20 mA (MOTOR CUR. 4- 20 mA) [39] [39]
Output current (pulse sequence), 0 - I
MAX
0 - 32000 p (MOTOR CUR. PULSE) [40] [40]
Output power, 0 - P
NOM
0-20 mA (MOTOR POWER 0-20 mA) [41] [41]
Output power, 0 - P
NOM
4-20 mA (MOTOR POWER 4-20 mA) [42] [42]
Output power (pulse sequence), 0 - P
NOM
0- 32000 p (MOTOR POWER PULSE) [43] [43]
Bus control, 0.0-100.0% 0-20 mA (BUS CONTROL 0-20 MA) [44] [44]
Bus control, 0.0-100.0% 4-20 mA (BUS CONTROL 4-20 MA) [45] [45]
Bus control (pulse sequence), 0.0-100.0% 0 - 32.000 Pulses (BUS CONTROL PULS) [46] [46]
Motor alteration (MOTOR ALTERATION) [50] [50]
Function:
This output can act both as a digital or an analog
output. If used as a digital output (data value [0]-[59]), a
0/24 V DC signal is transmitted; if used as an analoge
output, either a 0-20 mA signal, a 4-20 mA signal or a
pulse sequence of 0-32000 pulses is transmitted.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.83.A2.02 - VLT is a registered Danfoss trademark
125

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 8000 AQUA series and is the answer not in the manual?

Danfoss VLT 8000 AQUA series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 8000 AQUA series
CategoryDC Drives
LanguageEnglish

Related product manuals