VLT
®
8000 AQUA
■ Fuses
UL compliance
To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
200-240 V
VLT Bussmann SIBA Littel fuse Ferraz-Shawmut
8006 KTN-R30 5017906-032 KLN-R30 ATM-R30 or A2K-30R
8008 KTN-R50 5012406-050 KLN-R50 A2K-50R
8011, 8016 KTN-R60 5014006-063 KLN-R60 A2K-60R
8022 KTN-R80 5014006-080 KLN-R80 A2K-80R
8027, 8032 KTN-R125 2028220-125 KLN-R125 A2K-125R
8042 FWX-150 2028220-150 L25S-150 A25X-150
8052 FWX-200 2028220-200 L25S-200 A25X-200
8062 FWX-250 2028220-250 L25S-250 A25X-250
380-480 V
VLT Bussmann SIBA Littel fuse Ferraz-Shawmu
t
8006 KTS-R20 5017906-020 KLS-R20 ATM-R20 or A6K-20R
8008 KTS-R25 5017906-025 KLS-R25 ATM-R25 or A6K-25R
8011 KTS-R30 5012406-032 KLS-R30 ATM-R30 or A6
K-30R
8016, 8022 KTS-R40 5014006-040 KLS-R40 A6K-40R
8027 KTS-R50 5014006-050 KLS-R50 A6K-50R
8032 KTS-R60 5014006-063 KLS-R60 A6K-60R
8042 KTS-R80 2028220-100 KLS-R80 A6K-80R
8052 KTS-R100 2028220-125 KLS-R100 A6K-100R
8062 KTS-R125 2028220-12
5
KLS-R125 A6K-125R
8072 KTS-R150 2028220-160 KLS-R150 A6K-150R
8102 FWH-220 2028220-200 L50S-225 A50-P225
8122 FWH-250 2028220-25
0
L50S-250 A50-P250
8152* FWH-300/170M3017 2028220-315 L50S-300 A50-P300
8202* FWH-350/170M3018 2028220-315 L50S-350 A50-P350
8252* FWH-400/1
70M4012
206xx32-4
00
L50S-400 A50-P400
8302* FWH-500/170M4014 206xx32-500 L50S-500 A50-P500
8352* FWH-600/170M4016 206xx32-600 L50S-600 A50-P600
8452 170M4017 2061032-
700
6,9URD31
D08A0700
8502 170M6013 2063032-900 6,9URD33D08A0900
8602 170M6013 2063032-900 6,9URD33D08A0900
8652 170M6013 2063032-
900
6,9URD33
D08A0900
* Circuit Breakers manufactured by General Electric, Cat. No. SKHA36AT0800 with the rating plug listed
below can be used to meet UL requirement.
8152 rating plug No. SRPK800 A 300
8202 rating plug No. SRPK800 A 400
8252 rating plug No. SRPK800 A 400
8302 rating plug No. SRPK800 A 500
8352 rating plug No. SRPK800 A 600
MG.83.A2.02 - VLT is a registered Danfoss trademark
48