■ Technical data, mains supply 3 x 525 - 600 V
According to international requirements 8016 8022 8027 8032 8042 8052 8062 8072
Output current I
VLT,N
[A] (550 V) 18 23 28 34 43 54 65 81
I
VLT, MAX
(60 s) [A] (550V) 20 25 31 37 47 59 72 89
I
VLT,N
[A](575V) 17 22 27 3241 526277
I
VLT, MAX
(60 s) [A] (575 V) 19 24 30 35 45 57 68 85
Output S
VLT,N
[kVA] (550 V) 17 22 27 32 41 51 62 77
S
VLT,N
[kVA] (575 V) 17 22 27 32 41 52 62 77
Typical shaft output P
VLT,N
[kW] 11 15 18.5 22 30 37 45 55
Typical shaft output P
VLT,N
[HP] 15 20 25 30 40 50 60 75
Max. copper cable
cross-section to motor
and loadsharing
4)
[mm
2
] 16 16 16 3535 505050
[AWG]
2)
6 6 6 2 2 1/0 1/0 1/0
Min. cable
cross-section to motor
and loadsharing
3)
[mm
2
] 0.5 0.5 0.5 10 10 16 16 16
[AWG]
2)
20 20 20 8 8 6 6 6
Rated Input Current
I
VLT.N
[A] (550 V) 18 22 27 33 42 53 63 79
I
VLT.N
[A] (600 V) 16 21 25 30 38 49 38 72
[mm2] 16 16 16 3535 505050Max copper cable
cross section, power
4)
[AWG]
2)
6 6 6 2 2 1/0 1/0 1/0
Max. prefuses (mains)
1)
[-]/UL [A] 20 30 35 45 60 75 90 100
Efficiency 0.96
Weight IP 20/NEMA 1 [kg/Ibs]
23/
51
23/
51
23/
51
30/
66
30/
66
48/
106
48/
106
48/
106
Estimated power loss at max. load (550 V) [W] 451 576 702 852 1077 1353 1628 2029
Estimated power loss at max. load (600 V) [W] 446 576 707 838 1074 1362 1624 2016
Enclosure
IP 20/NEMA 1
1. For type of fuse, see section Fuses.
2. American Wire Gauge (AWG).
3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted
into
the terminals to comply with IP 20.
Always comply with national and local regulations on min. cable cross-section.
4. Aluminium cables with cross-section above 35 mm
2
must be connected by use of
an Al-Cu connector.
MG.83.A2.02 - VLT is a registered Danfoss trademark