11.2.10 Mixing Fan
The mixing fan snaps into a slot in the power terminal mounting plate. To remove or reinstall the mixing fan, use the
following steps. See Illustration 11.5.
Disassembly
1. Place the end of a screwdriver under each of the
mixing fan release tabs. Press in and lift to free
the fan and housing from the power terminal
mounting plate.
2. Unplug the mixing fan cable connector. Tape the
free end of the fan cable to the mounting plate
so that it does not fall back into the drive.
3. Remove the mixing fan from the fan housing.
Reassembly
1. Connect the fan cable to the mixing fan cable
connector.
2. Position the mixing fan in the fan housing.
3. Position the fan and housing in the fan slot on
the power terminal mounting plate.
4. Press the mixing fan into the slot until the release
tabs snap into place.
D2h/D4h/D7h/D8h/J9 Unit Dis...
VLT
®
FC Series, D1h–D8h, Da2/Db2/Da4/Db4, E1h–E4h, J8/J9
198 Danfoss A/S © 02/2019 All rights reserved. MG94A502
1111

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish

Related product manuals