4.
-
-
-
-
-
1.
-
-
2.
3.
Set switches A53 and A54 to select the signal type (U = voltage, I = current).
Example
e30bf146.10
BUS TER.
OFF-ON
A53 A54
U- I U- I
1
2
N O
1
2
N O
1
2
N O
1
2
N O
Illustration 62: Location of Switches A53 and A54
5.12 Setting Up RS485 Serial Communication
5.12.1 RS485 Features
RS485 is a 2-wire bus interface compatible with multi-drop network topology. This interface contains the following features:
Ability to select from the following communication protocols:
FC, FC MC, FC option
Modbus RTU
Metasys N2
FLN
BACnet
Functions can be programmed remotely using the protocol software and RS485 connection or in parameter group 8-** Commu-
nications and Options.
Selecting a specific communication protocol changes various default parameter settings to match the specifications of the pro-
tocol, making more protocol-specific parameters available.
Option cards for the drive are available to provide more communication protocols. See the option card documentation for in-
stallation and operation instructions.
A switch (BUS TER) is provided on the control card for bus termination resistance.
5.12.2 Configuring RS485 Serial Communication
Procedure
Connect RS485 serial communication wiring to terminals (+) XD2.2 and (-) XD2.3.
- Use shielded serial communication cable.
- Properly ground the wiring. Refer to
5.8.6 Connecting to Ground.
Select the protocol type in parameter 8-30 Protocol.
Select the drive address in parameter 8-31 Address.
AQ262141314214en-000301 / 130R0880 | 107Danfoss A/S © 2021.11
Electrical Installation
VLT® HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish

Related product manuals