Table 119: Fusible Disconnect Switches for N710–N800 Models, 525–690 V
N710
N800
IEC
1250 A/690 V
1250 A/690 V
ABB P/N
OS1250D30P
OS1250D30P
UL
1200 A/600 V
1200 A/600 V
ABB P/N
OS1200L30
OS1200L30
10.8.4 Non-fusible Disconnect Switches
The non-fusible disconnector switch is an option. All units ordered and supplied with a factory-installed, non-fusible disconnect
switch require a UL Class fuse to meet 65kA SCCR for the drive system.
Table 120: Non-fusible Disconnect Switches for N110–N315 Models, 380–480 V
N110
N132
N160
N200
N250
N315
IEC
400 A/690 V
400 A/690 V
400 A/690 V
630 A/690 V
630 A/690 V
630 A/690 V
ABB P/N
OT400E30
OT400E30
OT400E30
OT630E30
OT630E30
OT630E30
UL
400 A/600 V
400 A/600 V
400 A/600 V
600 A/600 V
600 A/600 V
800 A/600 V
ABB P/N
OT400U30
OT400U30
OT400U30
OT600U30
OT600U30
OT800U30
Table 121: Non-fusible Disconnect Switches for N355–N560 Models, 380–480 V
N355
N400
N450
N500
N560
IEC
1000 A/690 V
1000 A/690 V
1250 A/690 V
1250 A/690 V
1250 A/690 V
ABB P/N
OT1000E30
OT1000E30
OT1250E30
OT1250E30
OT1250E30
UL
800 A/600 V
1200 A/600 V
1200 A/600 V
1200 A/600 V
1200 A/600 V
ABB P/N
OT800U30
OT1200U30
OT1200U30
OT1200U30
OT1200U30
Table 122: Non-fusible Disconnect Switches for N110–N315 Models, 525–690 V
N110
N132
N160
N200
N250
N315
IEC
400 A/690 V
400 A/690 V
400 A/690 V
630 A/690 V
630 A/690 V
630 A/690 V
ABB P/N
OT400E30
OT400E30
OT400E30
OT630E30
OT630E30
OT630E30
UL
400 A/600 V
400 A/600 V
400 A/600 V
600 A/600 V
600 A/600 V
600 A/600 V
ABB P/N
OT400U30
OT400U30
OT400U30
OT600U30
OT600U30
OT600U30
Table 123: Non-fusible Disconnect Switches for N400–N630 Models, 525–690 V
N400
N450
N500
N560
N630
IEC
630 A/690 V
630 A/690 V
630 A/690 V
1000 A/690 V
1000 A/690 V
ABB P/N
OT630E30
OT630E30
OT630E30
OT1000E30
OT1000E30
UL
600 A/600 V
600 A/600 V
600 A/600 V
800 A/600 V
800 A/600 V
ABB P/N
OT600U30
OT600U30
OT600U30
OT800U30
OT800U30
AQ262141314214en-000301 / 130R0880172 | Danfoss A/S © 2021.11
Specifications
VLT® HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish

Related product manuals