Table 148: Power Losses for Line Reactor Option, 525–690 V
Model
525–550 V [W]
551–690 V [W]
NO
HO
NO
HO
N110
395
270
360
245
N132
552
395
504
360
N160
845
552
776
504
N200
817
511
745
470
N250
1170
817
1069
745
N315
1366
967
1250
883
N355
1842
1366
1681
1250
N400
1409
996
1293
919
N500
1744
1171
1595
1071
N560
2491
1921
2279
1757
N630
2786
2491
2786
2279
N710
2472
1845
2268
1686
N800
3361
2472
3069
2268
11.6.7 dU/dt Filter Losses
Table 149: Power Losses for dU/dt Filter Option, 380–480 V
Model
380–440 V [W]
441–480 V [W]
NO
HO
NO
HO
N110
350
244
281
199
N132
526
350
448
281
N160
327
223
300
190
N200
514
327
429
300
N250
834
565
710
472
N315
1251
834
1036
710
N355
713
593
573
480
N400
914
713
757
573
N450
1054
795
878
757
N500
1402
1158
1101
964
N560
1774
1402
1434
1101
AQ262141314214en-000301 / 130R0880192 | Danfoss A/S © 2021.11
Appendix
VLT® HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AHF 005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AHF 005 and is the answer not in the manual?

Danfoss VLT AHF 005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AHF 005
CategoryDC Drives
LanguageEnglish

Related product manuals