[101] Reference 0-20 mA Par. 3-00 [Min - Max] 0% = 0 mA; 100% = 20 mA
Par. 3-00 [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
[102] Feedback
[103] Motor current 0-20 mA Value is taken from par. 16-37. Inverter max. current (160% current) is equal to 20 mA.
Example: Inverter norm current (11 kW) = 24 A. 160 % = 38.4 A. Motor norm current = 22 A Read-
out 11.46 mA.
20
mA
x
22
A
38.4
A
= 11.46
mA
In case the norm motor current is equal to 20 mA, the output setting of par. 6-52 is:
I
VLT
Max
x
100
I
Motor
Norm
=
38.4
x
100
22
=175%
[104] Torque rel to lim 0-20 mA The torque setting is related to setting in par. 4-16
[105] Torque rel to rated motor torque
0-20 mA
The torque is related to the motor torque setting.
[106] Power 0-20 mA Taken from par. 1-20.
[107] Speed 0-20 mA Taken from par. 3-03. 20 mA = value in par. 3-03
[108] Torque ref. 0-20 mA Torque reference related to 160% torque.
[109] Max Out Freq 0-20 mA In relation to par. 4-19.
[130] Output freq. 4-20 mA 0 Hz = 4 mA, 100 Hz = 20 mA
[131] Reference 4-20 mA Par. 3-00 [Min-Max] 0% = 4 mA; 100% = 20 mA
Par. 3-00 [-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
[132] Feedback 4-20 mA
[133] Motor cur. 4-20 mA Value is taken from par. 16-37. Inverter max. current (160% current) is equal to 20 mA.
Example: Inverter norm current (11 kW) = 24 A. 160 % = 38.4 A. Motor norm current = 22 A Read-
out 11.46 mA.
16
mA
x
22
A
38.4
A
= 9.17
mA
In case the norm motor current is equal to 20 mA, the output setting of par. 6-52 is:
I
VLT
Max
x
100
I
Motor
Norm
=
38.4
x
100
22
=175%
[134] Torque % lim. 4-20 mA The torque setting is related to setting in par. 4-16.
[135] Torque % nom 4-20 mA The torque setting is related to the motor torque setting.
[136] Power 4-20 mA Taken from par. 1-20
[137] Speed 4-20 mA Taken from par. 3-03. 20 mA = Value in par. 3-03.
[138] Torque 4-20 mA Torque reference related to 160% torque.
[139] Bus ctrl. 0-20 mA An output value set from fieldbus process data. The output will work independently of internal
functions in the frequency converter.
[140] Bus ctrl. 4-20 mA An output value set from fieldbus process data. The output will work independently of internal
functions in the frequency converter.
[141] Bus ctrl. 0-20 mA, timeout Par. 4-54 defines the behaviour of the analog output in case of bus time-out.
[142] Bus ctrl. 4-20 mA, timeout Par. 4-54 defines the behaviour of the analog output in case of bus time-out.
[150] Max Out Freq 4-20 mA In relation to par. 4-19.
6-71 Terminal X45/1 Output Min Scale
Range: Function:
0.00%* [0.00 - 200.00%] Scale the minimum output of the selected analog signal at terminal X45/1, as a percentage of the
maximum signal value. E.g. if 0 mA (or 0 Hz) is desired at 25% of the maximum output value, then
programme 25%. Scaling values up to 100% can never be higher than the corresponding setting
in par. 6-72.
FC 300 Programming Guide 3 Parameter descriptions