6-72 Terminal X45/1 Output Max Scale
Range: Function:
100%* [0.00 - 200.00%] Scale the maximum output of the selected analog signal at terminal X45/1. Set the value to the
maximum value of the current signal output. Scale the output to give a current lower than 20 mA
at full scale; or 20 mA at an output below 100% of the maximum signal value. If 20 mA is the desired
output current at a value between 0 - 100% of the full-scale output, programme the percentage
value in the parameter, i.e. 50% = 20 mA. If a current between 4 and 20 mA is desired at maximum
output (100%), calculate the percentage value as follows (example where desired max. output is
10 mA):
I
RANGE
mA
I
DESIRED
MAX
mA
x
100 % =
20 − 4
mA
10
mA
x
100 % = 160 %
6-73 Terminal X45/1 Output Bus Control
Range: Function:
0.00%* [0.00 - 100.00%] Holds the level of Analog Output 3 (terminal X45/1) if controlled by bus.
6-74 Terminal X45/1 Output Timeout Preset
Range: Function:
0.00%* [0.00 - 100.00%] Holds the preset level of Analog Output 3 (terminal X45/1).
In case of a bus timeout and a timeout function is selected in par. 6-70 the output will preset to this
level.
3.8.10 6-8* Analog Output 4 MCB113
Parameters for configuring the scaling and limits for analog output 4. Terminal X45/3 and X45/4. Analog outputs are current outputs: 0/4 – 20 mA.
Resolution on analog output is 11 bit.
6-80 Terminal X45/3 Output
Option: Function:
Select the function of Terminal X45/3 as an analog current output.
[0] * No operation Same selections available as for par. 6-70
6-81 Terminal X45/3 Output Min Scale
Option: Function:
[0.00%] * 0.00 - 200.00% Scales the minimum output of the selected analog signal on terminal X45/3. Scale the minimum
value as a percentage of the maximum signal value, i.e. 0 mA (or 0 Hz) is desired at 25% of the
maximum output value and 25% is programmed. The value can never be higher than the corre-
sponding setting in par. 6-82 if value is below 100%.
This parameter is active when option module MCB 113 is mounted in the frequency converter.