6-72 Terminal X45/1 Output Max Scale
Range: Function:
100%* [0.00 - 200.00%] Scale the maximum output of the selected analog signal at terminal X45/1. Set the value to the
maximum value of the current signal output. Scale the output to give a current lower than 20 mA
at full scale; or 20 mA at an output below 100% of the maximum signal value. If 20 mA is the desired
output current at a value between 0 - 100% of the full-scale output, programme the percentage
value in the parameter, i.e. 50% = 20 mA. If a current between 4 and 20 mA is desired at maximum
output (100%), calculate the percentage value as follows (example where desired max. output is
10 mA):
I
RANGE
mA
I
DESIRED
MAX
mA
x
100 % =
20 4
mA
10
mA
x
100 % = 160 %
6-73 Terminal X45/1 Output Bus Control
Range: Function:
0.00%* [0.00 - 100.00%] Holds the level of Analog Output 3 (terminal X45/1) if controlled by bus.
6-74 Terminal X45/1 Output Timeout Preset
Range: Function:
0.00%* [0.00 - 100.00%] Holds the preset level of Analog Output 3 (terminal X45/1).
In case of a bus timeout and a timeout function is selected in par. 6-70 the output will preset to this
level.
3.8.10 6-8* Analog Output 4 MCB113
Parameters for configuring the scaling and limits for analog output 4. Terminal X45/3 and X45/4. Analog outputs are current outputs: 0/4 – 20 mA.
Resolution on analog output is 11 bit.
6-80 Terminal X45/3 Output
Option: Function:
Select the function of Terminal X45/3 as an analog current output.
[0] * No operation Same selections available as for par. 6-70
6-81 Terminal X45/3 Output Min Scale
Option: Function:
[0.00%] * 0.00 - 200.00% Scales the minimum output of the selected analog signal on terminal X45/3. Scale the minimum
value as a percentage of the maximum signal value, i.e. 0 mA (or 0 Hz) is desired at 25% of the
maximum output value and 25% is programmed. The value can never be higher than the corre-
sponding setting in par. 6-82 if value is below 100%.
This parameter is active when option module MCB 113 is mounted in the frequency converter.
3 Parameter descriptions FC 300 Programming Guide
126
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals