3-04 Reference Function
Option: Function:
[0] * Sum Sums both external and preset reference sources.
[1] External/Preset Use either the preset or the external reference source.
Shift between external and preset via a command on a digital input.
3.5.3 3-1* References
Parameters for setting up the reference sources.
Select the preset reference(s).
Select Preset ref. bit 0 / 1 / 2
[16], [17] or [18] for the corresponding digital inputs in par. group 5-1*.
3-10 Preset Reference
Array [8]
Range: 0-7
Range: Function:
0.00 %* [-100.00 - 100.00 %] Enter up to eight different preset references (0-7) in this parameter, using array programming. The
preset reference is stated as a percentage of the value Ref
MAX
(par. 3-03
Maximum Reference
) If a
Ref
MIN
different from 0 (par. 3-02
Minimum Reference
) is programmed, the preset reference is
calculated as a percentage of the full reference range, i.e. on the basis of the difference between
Ref
MAX
and Ref
MIN
. Afterwards, the value is added to Ref
MIN
. When using preset references, select
Preset ref. bit 0 / 1 / 2 [16], [17] or [18] for the corresponding digital inputs in parameter group
5-1*.
Preset ref. bit 2 1 0
Preset ref. 0 0 0 0
Preset ref. 1 0 0 1
Preset ref. 2 0 1 0
Preset ref. 3 0 1 1
Preset ref. 4 1 0 0
Preset ref. 5 1 0 1
Preset ref. 6 1 1 0
Preset ref. 7 1 1 1
3-11 Jog Speed [Hz]
Range: Function:
Application
dependent*
[Application dependant] The jog speed is a fixed output speed at which the frequency converter is running when the jog
function is activated.
See also par. 3-80
Jog Ramp Time
.
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
73