Type designation
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
Estimated power loss at rated maximum load [W]
(2)
44
60
88
120
160
220
300
Efficiency
(3)
0.96
0.96
0.96
0.96
0.96
0.96
0.96
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss
MyDrive® ecoSmart website.
3
Efficiency measured at nominal current. For energy efficiency class, see
8.4 Ambient Conditions. For part load losses, see Danfoss MyDrive® ecoS-
mart website.
Table 39: B2/B4 Enclosure, Mains Supply 525–690 V IP20/IP21/IP55 - Chassis/NEMA 1/NEMA 12 (FC 302 only), P11K–P22K
Type designation
P11K
P15K
P18K
P22K
High/normal overload
(1)
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 550 V [kW/(hp)]
7.5 (10)
11 (15)
11 (15)
15 (20)
15 (20)
18.5 (25)
18.5 (25)
22 (30)
Typical shaft output at 690 V [kW/(hp)]
11 (15)
15 (20)
15 (20)
18.5 (25)
18.5 (25)
22 (30)
22 (30)
30 (40)
Enclosure protection rating IP20
B4
B4
B4
B4
Enclosure protection rating IP21, IP55
B2
B2
B2
B2
Output current
Continuous (525–550 V) [A]
14
19
19
23
23
28
28
36
Intermittent (60 s overload) (525–550 V) [A]
22.4
20.9
30.4
25.3
36.8
30.8
44.8
39.6
Continuous (551–690 V) [A]
13
18
18
22
22
27
27
34
Intermittent (60 s overload) (551–690 V) [A]
20.8
19.8
28.8
24.2
35.2
29.7
43.2
37.4
Continuous kVA (at 550 V) [kVA]
13.3
18.1
18.1
21.9
21.9
26.7
26.7
34.3
Continuous kVA (at 690 V) [kVA]
15.5
21.5
21.5
26.3
26.3
32.3
32.3
40.6
Maximum input current
Continuous (at 550 V) (A)
15
19.5
19.5
24
24
29
29
36
Intermittent (60 s overload) (at 550 V) (A)
23.2
21.5
31.2
26.4
38.4
31.9
46.4
39.6
Continuous (at 690 V) (A)
14.5
19.5
19.5
24
24
29
29
36
Intermittent (60 s overload) (at 690 V) (A)
23.2
21.5
31.2
26.4
38.4
31.9
46.4
39.6
Additional specifications
Estimated power loss at rated maximum load
[W]
(2)
150
220
220
300
300
370
370
440
Efficiency
(3)
0.98
0.98
0.98
0.98
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss
MyDrive® ecoSmart website.
3
Efficiency measured at nominal current. For energy efficiency class, see
8.4 Ambient Conditions. For part load losses, see Danfoss MyDrive® ecoS-
mart website.
AQ267037727118en-000101 / 130R030068 | Danfoss A/S © 2021.01
Specifications
VLT® AutomationDrive FC 301/FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals