9 Application Examples
The examples in this section are intended as a quick
reference for common applications.
Parameters associated with the terminals and
their settings are shown next to the drawings.
Switch settings for analog terminals A53 or A54
are shown where required.
9.1 Programming a Closed-loop Drive
System
A closed-loop drive system usually consists of the
following:
Motor.
Drive.
Encoder as feedback system.
Transmission.
Gearbox.
Load.
e30bh107.10
Encoder
Motor
Gearbox
Load
Transmission
Illustration 9.1 Basic Set-up for Closed-loop Speed Control
9.2 Wiring for Open-loop Speed Control
Parameters
+10
V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
A53
U - I
0 – 10 V
+
-
e30bb926.11
FC
Function Setting
Parameter 6-10 Termi
nal 53 Low Voltage
0.07 V*
Parameter 6-11 Termi
nal 53 High Voltage
10 V*
Parameter 6-14 Termi
nal 53 Low Ref./
Feedb. Value
0 Hz
Parameter 6-15 Termi
nal 53 High Ref./
Feedb. Value
50 Hz
* = Default value
Notes/comments:
Assumptions are 0 V DC input
= 0 Hz speed and 10 V DC
input = 50 Hz speed.
Table 9.1 Analog Speed Reference (Voltage)
Parameters
+10
V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
+
-
FC
e30bb927.11
A53
U - I
4 - 20mA
Function Setting
Parameter 6-12 Terminal
53 Low Current
4 mA*
Parameter 6-13 Terminal
53 High Current
20 mA*
Parameter 6-14 Terminal
53 Low Ref./Feedb.
Value
0 Hz
Parameter 6-15 Terminal
53 High Ref./Feedb.
Value
50 Hz
* = Default value
Notes/comments:
Assumptions are 4 mA input =
0 Hz speed and 20 mA input =
50 Hz speed.
Table 9.2 Analog Speed Reference (Current)
Application Examples VLT® AutomationDrive FC 361
68 Danfoss A/S © 03/2019 All rights reserved. MG06K102
99

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 N110 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 N110 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361 N110
CategoryDC Drives
LanguageEnglish

Related product manuals