7.2.3 Entering System Information
NOTICE
SOFTWARE DOWNLOAD
For commissioning via PC, install MCT 10 Set-up
Software. The software is available for download (basic
version) or for ordering (advanced version, code number
130B1000). For more information and downloads, see
www.danfoss.com/en/service-and-support/downloads/dds/
vlt-motion-control-tool-mct-10/.
The following steps are used to enter basic system
information into the drive. Recommended parameter
settings are intended for start-up and checkout purposes.
Application settings vary.
NOTICE
Although these steps assume that an asynchronous
motor is used, a permanent magnet motor can be used.
For more information on specic motor types, see the
product-specic programming guide.
1. Press [Main Menu] on the LCP.
2. Select 0-** Operation/Display and press [OK].
3. Select 0-0* Basic Settings and press [OK].
4. Press [Quick Menus] on the LCP and then select
02 Quick Setup.
5. Change the following parameters settings listed
in Table 7.2 if necessary. The motor data is found
on the motor nameplate.
Parameter Default setting
Parameter 0-01 Language English
Parameter 1-20 Motor Power [kW] 4.00 kW
Parameter 1-22 Motor Voltage 400 V
Parameter 1-23 Motor Frequency 50 Hz
Parameter 1-24 Motor Current 9.00 A
Parameter 1-25 Motor Nominal Speed 1420 RPM
Parameter 5-12 Terminal 27 Digital Input Coast inverse
Parameter 3-02 Minimum Reference 0.000 RPM
Parameter 3-03 Maximum Reference 1500.000 RPM
Parameter 3-41 Ramp 1 Ramp up Time 3.00 s
Parameter 3-42 Ramp 1 Ramp Down Time 3.00 s
Parameter 3-13 Reference Site Linked to Hand/
Auto
Parameter 1-29 Automatic Motor Adaptation
(AMA)
O
Table 7.2 Quick Set-up Settings
NOTICE
MISSING INPUT SIGNAL
When the LCP shows AUTO REMOTE COASTING or alarm
60, External Interlock, the unit is ready to operate but is
missing an input signal. See chapter 5.8.4 Enabling Motor
Operation (Terminal 27) for details.
7.2.4 Conguring Automatic Energy
Optimization
Automatic energy optimization (AEO) is a procedure that
minimizes voltage to the motor, reducing energy
consumption, heat, and noise.
1. Press [Main Menu].
2. Select 1-** Load and Motor and press [OK].
3. Select 1-0* General Settings and press [OK].
4. Select parameter 1-03 Torque Characteristics and
press [OK].
5. Select either [2] Auto Energy Optim CT or [3] Auto
Energy Optim VT and press [OK].
7.2.5 Conguring Automatic Motor
Adaptation
Automatic motor adaptation is a procedure that optimizes
compatibility between the drive and the motor.
The drive builds a mathematical model of the motor for
regulating output motor current. The procedure also tests
the input phase balance of electrical power. It compares
the motor characteristics with the data entered in
parameters 1-20 to 1-25.
NOTICE
If warnings or alarms occur, see chapter 9.5 List of
Warnings and Alarms. Some motors are unable to run the
complete version of the test. In that case, or if an output
lter is connected to the motor, select [2] Enable reduced
AMA.
Run this procedure on a cold motor for best results.
1. Press [Main Menu].
2. Select 1-** Load and Motor and press [OK].
3. Select 1-2* Motor Data and press [OK].
4. Select parameter 1-29 Automatic Motor Adaptation
(AMA) and press [OK].
5. Select [1] Enable complete AMA and press [OK].
6. Press [Hand On] and then [OK].
The test runs automatically and indicates when it
is complete.