4.2 Network Connection
4.2.1 Ethernet Ports
The EtherNet/IP Module has 2 Ethernet ports. If only 1
connection is required, either port can be used.
4.2.2 Cables
Suitable cables for EtherNet/IP Module connection:
•
Category 5
•
Category 5e
•
Category 6
•
Category 6e
4.2.3 EMC Precautions
To minimize electromagnetic interference, Ethernet cables
should be separated from motor and mains cables by
200 mm (7.9 in).
The Ethernet cable must cross the motor and mains cables
at an angle of 90°.
1 3-phase supply
2 Ethernet cable
Illustration 4.1 Correct Running of Ethernet Cables
4.2.4 Network Establishment
The controller must establish communication directly with
each device before the device can participate in the
network.
4.3 Addressing
Each device in a network is addressed using a MAC
address and an IP address and can be assigned a symbolic
name associated with the MAC address.
•
The factory default is a static IP address
(192.168.1.2). The module also supports BootP
and DHCP addressing.
•
The symbolic name is optional and must be
congured within the device.
•
The MAC address is xed within the device and is
printed on a label on the front of the module.
Illustration 4.2 MAC ID Location