3 Installation
3.1 Installation Procedure
CAUTION
EQUIPMENT DAMAGE
If mains and control voltage are applied when installing
or removing options/accessories, it may damage the
equipment.
To avoid damage:
Remove mains and control voltage from the
soft starter before attaching or removing
options/accessories.
Installing the EtherNet/IP option:
1. Remove control power and mains supply from
the soft starter.
2. Fully pull out the top and bottom retaining clips
on the module (A).
3. Line up the module with the communication port
slot (B).
4. Push in the top and bottom retaining clips to
secure the module to the soft starter (C).
5. Connect Ethernet port 1 or port 2 on the module
to the network.
6. Apply control power to the soft starter.
177HA528.13
A
B
C
Illustration 3.1 Installing the EtherNet/IP Option
Remove the module from the soft starter:
1. Remove control power and mains supply from
the soft starter.
2. Disconnect all external wiring from the module.
3. Fully pull out the top and bottom retaining clips
on the module (A).
4. Pull the module away from the soft starter.
177HA378.12
A
Illustration 3.2 Removing the EtherNet/IP Option
Installation Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 7
3 3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Compact Starter MCD 201 and is the answer not in the manual?

Danfoss VLT Compact Starter MCD 201 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Compact Starter MCD 201
CategoryController
LanguageEnglish

Related product manuals