EasyManuals Logo
Home>Danfoss>Controller>VLT Compact Starter MCD 201

Danfoss VLT Compact Starter MCD 201 User Manual

Danfoss VLT Compact Starter MCD 201
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
7.2.3.2 Status Word (Read-only)
Use the structure in Table 7.6 to query the status of the soft starter.
Bit Function Details MCD 201 MCD 202 MCD 500
0 Ready 0 = Start or stop command not acceptable
1 = Start or stop command acceptable
1 Control from net 0 = Program mode
1 = Control from net
2 Coasting 0 = Coasting
1 = Enabled
3 Trip 0 = Not tripped
1 = Tripped
4 Reserved Must be 0
5 Reserved Must be 0
6 Reserved Must be 0
7 Warning 0 = No warning
1 = Warning
8 Ramping 0 = Not at full voltage (non-bypassed)
1 = Running (full voltage at the motor)
9 Local/remote 0 = Local control
1 = Remote control
10 Reserved Must be 0
11 On 0 = Unknown, not ready, ready to start, or tripped
1 = Starting, running, stopping, or jogging
12 Reserved Must be 0
13 Reserved Must be 0
14 Reserved Must be 0
15 Temperature limit 0 = Motor operating below normal operating temperature
1 = Motor operating above normal operating temperature
Table 7.6 Status Commands
Packet Structures Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 15
7 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Compact Starter MCD 201 and is the answer not in the manual?

Danfoss VLT Compact Starter MCD 201 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Compact Starter MCD 201
CategoryController
LanguageEnglish

Related product manuals