Mechanical dimensions, frame sizes E and F
Frame size F8 F9 F10 F11 F12 F13 F14
High overload
rated power -
160% overload
torque
250 - 400 kW
(380 - 500 V)
355 - 560 kW
(525-690 V)
250 - 400 kW
(380 - 500 V)
355 - 56 kW
(525-690 V)
450 - 630 kW
(380 - 500 V)
630 - 800 kW
(525-690 V)
710 - 800 kW
(380 - 500 V)
900 - 1200 kW
(525-690 V)
450 - 630 kW
(380 - 500 V)
630 - 800 kW
(525-690 V)
710 - 800 kW
(380 - 500 V)
900 - 1200 kW
(525-690 V)
1400 kW (525-690 V)
IP
NEMA
21, 54
Type 12
21, 54
Type 12
21, 54
Type 12
21, 54
Type 12
21, 54
Type 12
21, 54
Type 12
21, 54
Type 12
Shipping
dimensions [mm]
Height 2324 2324 2324 2324 2324 2324 2362
Width 970 1568 1760 2559 2160 2960 2578
Depth 1130 1130 1130 1130 1130 1130 1130
Drive dimensions
[mm]
Height
2204 2204 2204 2204 2204 2204 2262
Width 800 1400 1600 2400 2000 2800 2400
Depth 606 606 606 606 606 606 608
Max weight [kg] 440 656 880 1096 1022 1238 1410
NOTE
The F frames have seven different sizes, F8, F9, F10,F11, F12, and F14 The F8, F10 F12, and F14 consist of an inverter cabinet
on the right and rectifier cabinet on the left. The F9, F11 and F13 have an additional options cabinet left of the rectifier
cabinet. The F9 is an F8 with an additional options cabinet. The F11 is an F10 with an additional options cabinet. The F13 is
an F12 with an additional options cabinet.
How to Install
VLT
®
Automation Drive FC 300 12-Pulse
Operating Instructions High Power
14 MG34Q202 - VLT
®
is a registered Danfoss trademark
3
3