8.4 Warning and Alarm Definitions
Table 8.2 defines whether a warning is issued before an alarm, and whether the alarm trips the unit or trip locks the unit.
No. Description Warning Alarm/
Trip
Alarm/
Trip Lock
Parameter Reference
1 10 Volts low X
2 Live zero error (X) (X) 6-01 Live Zero Timeout Function
4 Mains phase loss (X) (X) (X) 14-12 Function at Mains Imbalance
5 DC link voltage high X
6 DC link voltage low X
7 DC overvoltage X X
8 DC undervoltage X X
9 Inverter overloaded X X
10 Motor ETR overtemperature (X) (X) 1-90 Motor Thermal Protection
11 Motor thermistor overtemperature (X) (X) 1-90 Motor Thermal Protection
12 Torque limit X X
13 Overcurrent X X X
14 Ground fault X X X
15 Hardware mismatch X X
16 Short Circuit X X
17 Control word timeout (X) (X) 8-04 Control Timeout Function
18 Start Failed
23 Internal Fan Fault X
24 External Fan Fault X 14-53 Fan Monitor
25 Brake resistor short-circuited X
26 Brake resistor power limit (X) (X) 2-13 Brake Power Monitoring
27 Brake chopper short-circuited X X
28 Brake check (X) (X) 2-15 Brake Check
29 Drive overtemperature X X X
30 Motor phase U missing (X) (X) (X) 4-58 Missing Motor Phase Function
31 Motor phase V missing (X) (X) (X) 4-58 Missing Motor Phase Function
32 Motor phase W missing (X) (X) (X) 4-58 Missing Motor Phase Function
33 Inrush fault X X
34 Fieldbus communication fault X X
35 Out of frequency range X X
36 Mains failure X X
37 Phase Imbalance X X
38 Internal fault X X
39 Heatsink sensor X X
40 Overload of Digital Output Terminal 27 (X) 5-00 Digital I/O Mode, 5-01 Terminal 27 Mode
41 Overload of Digital Output Terminal 29 (X) 5-00 Digital I/O Mode, 5-02 Terminal 29 Mode
42 Overload of Digital Output On X30/6 (X) 5-32 Term X30/6 Digi Out (MCB 101)
42 Overload of Digital Output On X30/7 (X) 5-33 Term X30/7 Digi Out (MCB 101)
46 Pwr. card supply X X
47 24 V supply low X X X
48 1.8 V supply low X X
49 Speed limit X (X) 1-86 Trip Speed Low [RPM]
50 AMA calibration failed X
51 AMA check U
nom
and I
nom
X
52 AMA low I
nom
X
Warnings and Alarms Instruction Manual
64 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG16E222
88

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals