ALARM 29, Heatsink temp
The maximum temperature of the heatsink has been
exceeded. The temperature fault will not reset until the
temperature falls below a defined heatsink temperature.
The trip and reset points are different based on the
adjustable frequency drive power size.
Troubleshooting
Check for the following conditions.
Ambient temperature too high.
Motor cable too long.
Incorrect airflow clearance above and below the
adjustable frequency drive.
Blocked airflow around the adjustable frequency
drive.
Damaged heatsink fan.
Dirty heatsink.
ALARM 30, Motor phase U missing
Motor phase U between the adjustable frequency drive
and the motor is missing.
Remove power from the adjustable frequency drive and
check motor phase U.
ALARM 31, Motor phase V missing
Motor phase V between the adjustable frequency drive
and the motor is missing.
Remove power from the adjustable frequency drive and
check motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the adjustable frequency drive
and the motor is missing.
Remove power from the adjustable frequency drive and
check motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period. Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The serial communication bus on the communication
option card is not working.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the adjustable frequency drive is lost and 14-10 Mains
Failure is NOT set to [0] No Function. Check the fuses to the
adjustable frequency drive and line power supply to the
unit.
ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
Table 8.3 is displayed.
Troubleshooting
Cycle power
Check that the option is properly installed
Check for loose or missing wiring
It may be necessary to contact your Danfoss supplier or
service department. Note the code number for further
troubleshooting directions.
No. Text
0 Serial port cannot be initialized. Contact your
Danfoss supplier or Danfoss Service Department.
256-258 Power EEPROM data is defective or too old.
Replace power card.
512-519 Internal fault. Contact your Danfoss supplier or
Danfoss Service Department.
783 Parameter value outside of min/max limits
1024-1284 Internal fault. Contact your Danfoss supplier or the
Danfoss Service Department.
1299 Option SW in slot A is too old
1300 Option SW in slot B is too old
1302 Option SW in slot C1 is too old
1315 Option SW in slot A is not supported (not allowed)
1316 Option SW in slot B is not supported (not allowed)
1318 Option SW in slot C1 is not supported (not
allowed)
1379-2819 Internal fault. Contact your Danfoss supplier or
Danfoss Service Department.
2561 Replace control card
2820 LCP stack overflow
2821 Serial port overflow
2822 USB port overflow
3072-5122 Parameter value is outside its limits
5123 Option in slot A: Hardware incompatible with
control board hardware
5124 Option in slot B: Hardware incompatible with
control board hardware
5125 Option in slot C0: Hardware incompatible with
control board hardware
5126 Option in slot C1: Hardware incompatible with
control board hardware
5376-6231 Internal fault. Contact your Danfoss supplier or
Danfoss Service Department.
Table 8.3 Internal Fault Codes
Warnings and Alarms
Instruction Manual
MG16E222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 69
8 8

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals