1)
For type of fuse, see chapter 10.3 Fuse Specifications
2)
American Wire Gauge
3)
Measured using 16 ft [5 m] shielded motor cables at rated load and rated frequency
4)
The typical power loss is at normal load conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable
conditions).
Values are based on a typical motor efficiency. Lower efficiency motors will also add to the power loss in the adjustable frequency drive
and vice versa.
If the switching frequency is raised from nominal, the power losses may rise significantly.
LCP and typical control card power consumption values are included. Further options and customer load may add up to 30 W to the
losses. (Though typically only 4 W extra for a fully loaded control card or options for slot A or slot B, each.)
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (±5%).
5)
Motor and line cable: 300 MCM/150 mm
2
6)
A2+A3 may be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 Enclosure kit in the Design
Guide.
7)
B3+4 and C3+4 may be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 Enclosure kit in the
Design Guide.
Table 10.8 Line Power Supply 3x525–690 V AC – Normal overload 110% for 1 minute
Specifications Instruction Manual
84 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG16E222