Digital inputs
Programmable digital inputs 4 (6)
1)
Terminal number 18, 19, 27
1)
, 29
1)
, 32, 33,
Logic PNP or NPN
Voltage level 0–24 V DC
Voltage level, logic'0' PNP <5 V DC
Voltage level, logic'1' PNP >10 V DC
Voltage level, logic '0' NPN
2)
>19 V DC
Voltage level, logic '1' NPN
2)
<14 V DC
Maximum voltage on input 28 V DC
Pulse frequency ranges 0–110 kHz
(Duty cycle) Min. pulse width 4.5 ms
Input resistance, R
i
Approx. 4
Safe Torque Off Terminal 37
3, 4)
(Terminal 37 is fixed PNP logic)
Voltage level 0–24 V DC
Voltage level, logic'0' PNP <4 V DC
Voltage level, logic'1' PNP >20 V DC
Maximum voltage on input 28 V DC
Typical input current at 24 V 50 mA rms
Typical input current at 20 V 60 mA rms
Input capacitance 400 nF
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1)
Terminals 27 and 29 can also be programmed as output.
2)
Except Safe Torque Off input Terminal 37.
3)
See chapter 2.4.6.6 Terminal 37 for further information about terminal 37 and Safe Torque Off.
4)
When using a contactor with a DC coil inside in combination with Safe Torque Off, it is important to make a return way for
the current from the coil when turning it off. This can be done by using a freewheel diode (or, alternatively, a 30 or 50 V MOV for
quicker response time) across the coil. Typical contactors can be bought with this diode.
Analog inputs
Number of analog inputs 2
Terminal number 53, 54
Modes Voltage or current
Mode select Switch S201 and switch S202
Voltage mode Switch S201/switch S202 = OFF (U)
Voltage level -10 to +10 V (scaleable)
Input resistance, R
i
Approx. 10 kΩ
Max. voltage ±20 V
Current mode Switch S201/switch S202 = ON (I)
Current level 0/4 to 20 mA (scaleable)
Input resistance, R
i
Approx. 200 Ω
Max. current 30 mA
Resolution for analog inputs 10 bit (+ sign)
Accuracy of analog inputs Max. error 0.5% of full scale
Bandwidth 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Specifications
Instruction Manual
86 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG16E222
1010

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals