4.14.4 18-9* PID Readouts
18-90 Process PID Error
Default value: 0.0%
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: int16
Change during operation: False
View the error value in the process PID controller.
Table 353: Range:
Min: -200.0%
Max: 200.0%
Default value: 0.0%
18-91 Process PID Output
Default value: 0.0%
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: int16
Change during operation: False
View the raw output value from the process PID controller.
Table 354: Range:
Min: -200.0%
Max: 200.0%
Default value: 0.0%
18-92 Process PID Clamped Output
Default value: 0.0%
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: int16
Change during operation: False
View the output value from the process PID controller after reaching a clamp limit.
Table 355: Range:
Min: -200.0%
Max: 200.0%
Default value: 0.0%
18-93 Process PID Gain Scaled Output
Default value: 0.0%
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: int16
Change during operation: False
View the output value from the process PID controller after reaching a clamp limit, and scaling the resulting value with considera-
tions to the gain.
Table 356: Range:
Min: -200.0%
Max: 200.0%
Default value: 0.0%
4.15 Parameter Group 20-** Drive Closed Loop
This parameter group is used for configuring the closed loop PI controller that controls the output frequency of the drive.
4.15.1 20-0* Feedback
This parameter group is used to configure the feedback signal for the closed-loop PI control of the drive.
20-00 Feedback 1 Source
Default value: [0] No function
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
This parameter defines which input is used as the source of the feedback signal.
AU363928304090en-000101 / 130R0982 | 157Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals