Table 93: Option:
The brake resistor is not active.
2-16 AC Brake, Max current
Change during operation: True
Enter the maximum permissible current when using the AC brake to avoid overheating motor windings.
Table 94: Range:
2-17 Over-voltage Control
Default value: [2] Enabled
Change during operation: True
Select whether to enable OVC during ramp down, which reduces the risk of drive trip due to overvoltage on the DC link caused by
generative power from load.
Table 95: Option:
Activates OVC when the drive is not in the stop state.
Activates OVC.
N O T I C E
The ramp time is automatically adjusted to avoid tripping of the drive.
2-19 Over-voltage Gain
Change during operation: True
This parameter enables the user to fine tune the overvoltage gain for parameter 2-17 Over-voltage Control. It is not necessary to
change this parameter for normal applications.
Table 96: Range:
4.5 Parameter Group 3-** Reference/Ramps
4.5.1 3-0* Reference Limits
Parameters for setting the reference unit, limits, and ranges. Also see parameter group 20-0* Feedback for information on settings in
closed loop.
3-02 Minimum Reference
Change during operation: True
AU363928304090en-000101 / 130R0982 | 59Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide