Set the duration of the DC-brake current set in parameter 2-01 DC Brake Current, once activated.
Table 89: Range:
Min: 0 s
Max: 60 s
Default value: 10 s
2-04 DC Brake Cut In Speed
Default value: 0 Hz
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
This parameter is for setting the DC-brake cut-in speed at which parameter 2-01 DC Brake Current is to be active with a stop com-
mand.
Table 90: Range:
Min: 0 Hz
Max: 500 Hz
Default value: 0 Hz
2-06 Parking Current
Default value: 100%
Parameter type: Range
2-setup: All setups
Conversion index: -
Data type: u_int16
Change during operation: True
Set current as percentage of rated motor current, parameter 1-24 Motor Current. Active with parameter 1-73 Flying Start. The parking
current is active during the time period set in parameter 2-07 Parking Time.
N O T I C E
Parameter 2-06 Parking Current is only active when 1 of the PM motor construction options is selected in parameter 1-10 Motor
Construction.
Table 91: Range:
Min: 0%
Max: 150%
Default value: 100%
2-07 Parking Time
Default value: 3 s
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
Set the duration of the parking current time set in parameter 2-06 Parking Current. Active with parameter 1-73 Flying Start.
N O T I C E
Parameter 2-07 Parking Time is only active when options of parameter 1-10 Motor Construction are set to enable PM motors.
Table 92: Range:
Min: 0.1 s
Max: 60 s
Default value: 3 s
4.4.2 2-1* Brake Energy Function
Parameter group for selecting dynamic brake parameters.
2-10 Brake Function
Default value: [0] Off
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
AU363928304090en-000101 / 130R098258 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals