14-64 Dead Time Compensation Zero Current Level
Default value: [0] Disabled
Change during operation: False
If a long motor cable is used, set the parameter to [1] Enabled to minimize the motor-torque ripple.
Table 262: Option:
14-65 Speed Derate Dead Time Compensation
Default value: Configuration dependent
Change during operation: False
Dead-time compensation level is reduced linearly from the maximum level of the output frequency set in parameter 14-07 Dead
Time Compensation Level to the minimum level of the output frequency set in this parameter.
Table 263: Range:
Default value: Configuration dependent
4.11.8 14-9* Fault Settings
The parameter group for fault customization settings.
14-90 Fault Level
Default value: [3] Trip lock
Change during operation: False
Use this parameter to customize fault levels. Only index 7, which indicates overcurrent faults, is supported.
Table 264: Option:
Alarm is set to trip lock level.
Alarm is configured into trip alarm, which can be reset after a delay time. For example, if overcurrent
alarm is configured to this option, it can be reset 3 minutes after the alarm is reported.
The drive tries to catch a motor spinning when starting. If this option is selected, parameter 1-73 Flying
Start is set to [1] Enabled.
4.12 Parameter Group 15-** Drive Information
Parameter group containing drive information such as operating data, hardware configuration, and software versions.
4.12.1 15-0* Operating Data
15-00 Operating hours
Change during operation: True