22-82 Work Point Calculation
Default value: [0] Disabled
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Table 412: Option:
[0]
Disabled
Disable calculation of working point at rated speed.
[1]
Enabled
Enable calculation of working point at rated speed.
22-84 Speed at No-Flow [Hz]
Default value: Configuration dependent
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
Set the motor speed in Hz at which flow is 0 and minimum pressure is achieved.
Table 413: Range:
Min: 0 Hz
Max: 400.0 Hz
Default value: Configuration dependent
22-86 Speed at Design Point [Hz]
Default value: Configuration dependent
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
Set the motor speed in Hz at which system design working point is achieved.
Table 414: Range:
Min: 0 Hz
Max: 400.0 Hz
Default value: Configuration dependent
22-87 Pressure at No-Flow Speed
Default value: 0
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: u_int32
Change during operation: True
Set the pressure value corresponding to speed at no flow.
Table 415: Range:
Min: 0
Max: 4999.000
Default value: 0
22-88 Pressure at Rated Speed
Default value: 4999.000
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: u_int32
Change during operation: True
Set the pressure value corresponding to pressure at rated speed.
Table 416: Range:
Min: 0
Max: 4999.000
Default value: 4999.000
22-89 Flow at Design Point
Default value: 0
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: int32
Change during operation: True
Set the flow value corresponding to flow at design point.
AU363928304090en-000101 / 130R0982176 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals