Table 113: Range:
Min: 0.1 Hz
Max: 400.0 Hz
Default value: 100 Hz
4-18 Current Limit
Default value: 110%
Parameter type: Range
2-setup: All setups
Conversion index: -
Data type: u_int16
Change during operation: True
Enter the current limit for motor and generator operation. Parameter 4-18 Current Limit will be changed automatically if nominal
motor current (parameter 1-24 Motor Current) is updated.
Table 114: Range:
Min: 0%
Max: 1000%
Default value: 110%
4-19 Max Output Frequency
Default value: 100.0 Hz
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: False
Enter the maximum output frequency, which defines the absolute limit on the drive output frequency for improved safety in appli-
cations where unintended overspeeding must be avoided. This absolute limit applies to all configurations and is independent of the
setting in parameter 1-00 Configuration Mode.
When parameter 1-10 Motor Construction is set to 1 of the options enabling PM motor construction, the maximum limit of parameter
4-19 Max Output Frequency might be limited by the setting of parameter 1-40 Back EMF at 1000 RPM to avoid a too high Back EMF,
which can damage the drive. If parameter 4-19 Max Output Frequency is set lower than parameter 4-14 Motor Speed High Limit [Hz],
the value of parameter 4-14 Motor Speed High Limit [Hz] is adjusted to the same value as parameter 4-19 Max Output Frequency auto-
matically.
Table 115: Range:
Min: 0 Hz
Max: 400 Hz
Default value: 100.0 Hz
4.6.2 4-4* Adjustable Warnings 2
4-40 Warning Freq. Low
Default value: 0 Hz
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
Use this parameter to set a lower limit for the frequency range. When the motor speed drops below this limit, the display reads
SPEED LOW. Warning bit 10 is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be configured to
indicate this warning. The LCP warning indicator light is not turned on when this parameter set limit is reached.
Table 116: Range:
Min: 0 Hz
Max: 500 Hz
Default value: 0 Hz
4-41 Warning Freq. High
Default value: 100 Hz
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
Use this parameter to set a higher limit for the frequency range. When the motor speed exceeds this limit, the display reads SPEED
HIGH. Warning bit 9 is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be configured to indicate
this warning. The LCP warning indicator light is not turned on when this parameter set limit is reached.
Table 117: Range:
Min: 0 Hz
Max: 500 Hz
Default value: 100 Hz
AU363928304090en-000101 / 130R0982 | 65Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals