Category 5
Category 5e
Category 6
Category 6e
4.2.3 EMC Precautions
To minimize electromagnetic interference, Ethernet cables should be separated from motor and mains cables by 200 mm (7.9 in).
If the Ethernet cable must cross motor or mains cables, the crossing should be at an angle of 90°.
4.3 Network Establishment
The controller must establish communications directly with each device before the device can participate in the network.
4.4 Addressing
Each device in a network is addressed using a MAC address and an IP address.
The device can be assigned a static IP address during configuration or can be configured to accept a dynamic IP address (via
DHCP).
The MAC address is fixed within the device and is printed on a label on the front of the device.