8.3.2 Vendor-specific Objects
The EtherNet/IP module supports vendor-specific classes 100, 101, 102, 103, and 104.
8.3.2.1 Class 100 ~ 102 Objects (Read/Write)
Class 100 ~ 102 objects allow parameter values to be read from and written to the soft starter.
Class 100d (0x64): Parameters 1–99
Class 101d (0x65): Parameters 100–199
Class 102d (0x66): Parameters 200~299
N O T I C E
Parameter lists vary according to the model and version of the soft starter. See the relevant soft starter operating guide for a
complete parameter list.
N O T I C E
When writing parameter values, the EtherNet/IP module will update all parameter values in the soft starter. Always enter a valid
value for every parameter.
N O T I C E
Changing the values of the Factory parameters (parameter group 20-**) may cause unpredictable behavior in the soft starter. Con-
sult a local supplier before adjusting the Factory parameters.
8.3.2.2 Class 103 Objects (Read Only)
Class 103d (0x67) allows soft starter state information to be read from the soft starter.
Table 6: Objects to be Read from the Soft Starter
Soft starter state
1 = Ready
2 = Starting
3 = Running
4 = Stopping (including braking)
5 = Restart delay (including temperature check)
6 = Tripped
7 = Programming mode
8 = Jog forward
AN427641276310en-000101 / 175R118726 | Danfoss A/S © 2022.10
Packet Structures
EtherNet/IP Module
Installation Guide