8.2.2.3 Command Examples
Byte
Value
Description
0
0b01000000 (64d, 0x40)
Command: Start the soft starter.
1
0b00000000 (00d, 0x00) or
0b00100000 (32d, 0x20)
Command: Select primary or secondary motor settings when starting.
0
0b10000000 (128d, 0x80)
Command: Reset the soft starter.
The reset only occurs when the previous reset bit is 0, otherwise the value of 1 is ig-
nored.
0
0b11000000 (192d, 0xC0)
Command: Reset and start the soft starter.
0
0bX0000000 (00d, 0x00)
Command: Stop the soft starter.
8.2.3 Status Information (Assembly Instance 154d)
To retrieve status data from the soft starter, use assembly class 04d (0x04), assembly instance 154d (0x9A), attribute 03d (0x03).
8.2.3.1 Bytes 0–1: Starter State
Bits
Function
Details
0
Ready
0 = Not ready
1 = Ready to start
1
Operating mode
0 = Program mode
1 = Operating mode
2
Running
0 = Not ready, ready to start, or tripped
1 = Starting, Running, Stopping, or Jogging
3
Trip
0 = Not tripped
1 = Tripped
4
Jog forward
1 = Jog forward
5
Jog reverse
1 = Jog reverse
6
Reserved
7
Warning
0 = No warning
1 = Warning
8
Ramping
1 = Running (full voltage at the motor)
9
Local/remote
0 = Hand on
1 = Auto on
10
Reserved
11
Reserved
12
Reserved
AN427641276310en-000101 / 175R118724 | Danfoss A/S © 2022.10
Packet Structures
EtherNet/IP Module
Installation Guide

Table of Contents

Other manuals for Danfoss VLT MCD 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 202 and is the answer not in the manual?

Danfoss VLT MCD 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 202
CategoryController
LanguageEnglish

Related product manuals