8.2.2.3 Command Examples
Command: Start the soft starter.
0b00000000 (00d, 0x00) or
0b00100000 (32d, 0x20)
Command: Select primary or secondary motor settings when starting.
Command: Reset the soft starter.
The reset only occurs when the previous reset bit is 0, otherwise the value of 1 is ig-
nored.
Command: Reset and start the soft starter.
Command: Stop the soft starter.
8.2.3 Status Information (Assembly Instance 154d)
To retrieve status data from the soft starter, use assembly class 04d (0x04), assembly instance 154d (0x9A), attribute 03d (0x03).
8.2.3.1 Bytes 0–1: Starter State
0 = Not ready
1 = Ready to start
0 = Program mode
1 = Operating mode
0 = Not ready, ready to start, or tripped
1 = Starting, Running, Stopping, or Jogging
0 = Not tripped
1 = Tripped
0 = No warning
1 = Warning
1 = Running (full voltage at the motor)