Bits
Function
Details
13
Reserved
14
Reserved
15
Temperature limit
0 = Motor operating within thermal capacity (thermal model)
1 = Motor operating above thermal capacity (thermal model)
8.2.3.2 Bytes 2–3: Reserved
Bits
Function
Details
0–15
Reserved
8.2.3.3 Bytes 4–7: Motor Current
Bits
Function
Details
0–31
Motor current
Average rms current across all 3 phases. Measured current is shown as a 32-bit value to 2 decimal places.
10d (0x0A) = 0.10 A
3450d (0xD7A) = 34.50 A
68930d (0x10D42) = 689.30 A
8.2.3.4 Bytes 8–9: Trip Code
Bits
Function
Details
0–15
Trip code
See the chapter Trip Codes.
8.2.3.5 Bytes 10–11: Reserved
Bits
Function
Details
0–15
Reserved
8.3 Explicit Messaging (Acyclic Operation)
This section provides information on objects, instances, attributes, and services for acyclic operation (explicit messaging).
All data is in little endian format.
8.3.1 Identity Object (Class 0x01)
Table 5: Supported Attributes for Identity Objects
Attribute
Function
Value
1
Vendor
204d (0xCC)
2
Device type
12d (0x0C)
3
Product code
269d (0x10D)
4
Revision: Major, minor
EDS file version
5
Status
Supported
6
Serial number
Supported
7
Product name
Supported
AN427641276310en-000101 / 175R1187 | 25Danfoss A/S © 2022.10
Packet Structures
EtherNet/IP Module
Installation Guide

Table of Contents

Other manuals for Danfoss VLT MCD 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 202 and is the answer not in the manual?

Danfoss VLT MCD 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 202
CategoryController
LanguageEnglish

Related product manuals