4.2.5. 1-7* Start Adjustments
Considering the need for various start functions in different applications, it is possible to select a number of functions in this parameter group.
1-71 Start Delay
Range: Function:
The start delay defines the time to pass from a start command is given until the motor starts accelerating.
Setting start delay to 0.0 sec. disables
Start Function
, [1-72], when start command is given.
0.0 s
*
[0.0 - 10.0 s]
Enter the time delay required before commencing acceleration.
Par. 1-72
Start Function
is active during
Start delay time
.
1-72 Start Function
Option: Function:
[0] DC Hold/Delay Time Motor is energized with DC holding current (par. 2-00) during start delay time.
[1] DC Brake/Delay Time Motor is energized with DC braking current (par. 2-01) during start delay time.
[2]
*
Coast/Delay Time Inverter is coasted during start delay time (inverter off).
1-73 Flying Start
Option: Function:
The Flying Start parameter is used to catch a spinning motor after eg. mains drop-out.
This function is not suitable for hoisting applications.
[0]
*
Disabled Flying start is not required.
[1] Enabled Frequency converter enabled to catch spinning motor.
NB!
When flying start is enabled par. 1-71,
Start Delay
, and par. 1-72,
Start Function
, have no
function.
4.2.6. 1-8* Stop Adjustments
To meet the need for various stop functions in different application these parameters offer some special stop features for the motor.
1-80 Function at Stop
Option: Function:
The selected function at stop is active in following situations:
Stop command is given and output speed is ramped down to
Min. Speed for Activating Functions at
Stop
.
Start command is removed (standby), and output speed is ramped down to
Min. Speed for Activating
Functions at Stop
.
DC-brake command is given, and DC-brake time has passed
While running and calculated output speed is below
Min. Speed for Activating Functions at Stop
.
[0]
*
Coast The inverter is coasted.
[1] DC hold The motor is energized with a DC current. See par. 2-00
DC Hold Current
for more information.
1-82 Min. Speed For Function at Stop [Hz]
Range: Function:
0.0 Hz
*
[0.0 - 20.0 Hz]
Set the speed at which to activate par. 1-80
Function at Stop
.
4. Parameter Descriptions VLT
p
Micro Drive FC 51
20
MG.02.C4.02 - VLT
p
is a registered Danfoss trademark
4

Other manuals for Danfoss VLT Micro Drive FC 51 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 Series and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive FC 51 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals