Illustration 4.6 Mains, Motor, and Grounding Connection for
Single-phase Units
Illustration 4.7 Mains, Motor, and Grounding Connection for 3-
phase Units
4.7
AC Mains Connection
4.7.1 AC Mains Connection
•
Size the wiring based on the input current of the
frequency converter. For maximum wire sizes, see
chapter 9.1 Electrical Data.
•
Comply with local and national electrical codes
for cable sizes.
Procedure
1. Connect the AC input power cables to terminals
N and L for single-phase units (see
Illustration 4.6), or to terminals L1, L2, and L3 for
3-phase units (see Illustration 4.7).
2. Depending on the
conguration of the
equipment, connect the input power to the
mains input terminals or the input disconnect.
3. Ground the cable in accordance with the
grounding instructions in chapter 4.3 Grounding.
4. When supplied from an isolated mains source (IT
mains or
oating delta) or TT/TN-S mains with a
grounded leg (grounded delta), ensure that the
RFI lter screw is removed, to avoid damage to
the intermediate circuit and reduce ground
capacity currents in accordance with IEC 61800-3.
Electrical Installation Operating Instructions
MG07A102 Danfoss A/S © 11/2015 All rights reserved. 15